MAXinBOX 66
Technical Support:
30
400, 429, 458, 487, 516, 545
1 Bit
I
C - - W -
DPT_Ack
0/1
[Ix] Presence: Slave Input
0 = Nothing; 1 = Detection
from slave device
401, 430, 459, 488, 517, 546
2 Bytes
I
C - - W -
DPT_TimePeriodSec
0-65535
[Ix] Presence: Waiting Time
0-65535 s.
402, 431, 460, 489, 518, 547
2 Bytes
I
C - - W -
DPT_TimePeriodSec
1-65535
[Ix] Presence: Listening Time
1-65535 s.
403, 432, 461, 490, 519, 548
1 Bit
I
C - - W -
DPT_Enable
0/1
[Ix] Presence: Enable
According to parameters
404, 433, 462, 491, 520, 549
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] Presence: Day/Night
According to parameters
405, 434, 463, 492, 521, 550
1 Bit
O
C T R - -
DPT_Occupancy
0/1
[Ix] Presence: Occupancy
State
0 = Not Occupied; 1 =
Occupied
406, 435, 464, 493, 522, 551
1 Bit
I
C - - W -
DPT_Ack
0/1
[Ix] External Motion Detection
0 = Nothing; 1 = Motion
detected by an external
sensor
407, 412, 417, 436, 441, 446, 465, 470, 475, 494,
499, 504, 523, 528, 533, 552, 557, 562
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] [Cy] Detection State
(Scaling)
0-100%
408, 413, 418, 437, 442, 447, 466, 471, 476, 495,
500, 505, 524, 529, 534, 553, 558, 563
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] [Cy] Detection State
(HVAC)
Auto, Comfort, Standby,
Economy, Building
Protection
409, 414, 419, 438, 443, 448, 467, 472, 477, 496,
501, 506, 525, 530, 535, 554, 559, 564
1 Bit
O
C T R - -
DPT_Switch
0/1
[Ix] [Cy] Detection State
(Binary)
Binary Value
410, 415, 420, 439, 444, 449, 468, 473, 478, 497,
502, 507, 526, 531, 536, 555, 560, 565
1 Bit
I
C - - W -
DPT_Enable
0/1
[Ix] [Cy] Enable Channel
According to parameters
411, 416, 421, 440, 445, 450, 469, 474, 479, 498,
503, 508, 527, 532, 537, 556, 561, 566
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] [Cy] Force State
0 = No Detection; 1 =
Detection