MAXinBOX 66
Technical Support:
29
1 Byte
C T - - -
DPT_Value_1_Ucount
0 - 255
[Ix] [Long Press] Constant
Value (Integer)
0 - 255
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Double Press] 0
Sending of 0
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Double Press] 1
Sending of 1
1 Bit
I
C T - W -
DPT_Switch
0/1
[Ix] [Double Press] 0/1
Switching
Switching 0/1
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Ix] [Double Press] Save
Scene
Sending of 128 - 191
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Ix] [Double Press] Run Scene
Sending of 0 - 63
359, 365, 371, 377, 383, 389
1 Bit
C T - - -
DPT_Trigger
0/1
[Ix] [Long Press/Release]
Stop Shutter
Release -> Stop Shutter
1 Bit
I
C - - W -
DPT_Reset
0/1
[Ix] [Pulse Counter] Reset
0 = No Action; 1 = Reset
360, 366, 372, 378, 384, 390
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Ix] [Long Press] Dimming
Status (Input)
0% - 100%
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Ix] [Long Press] Shutter
Status (Input)
0% = Top; 100% =
Bottom
391
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Motion Detector] Scene Input
Scene Value
392
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Motion Detector] Scene
Output
Scene Value
393, 422, 451, 480, 509, 538
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] Luminosity
0-100%
394, 423, 452, 481, 510, 539
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Open Circuit Error
0 = No Error; 1 = Open
Circuit Error
395, 424, 453, 482, 511, 540
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Short Circuit Error
0 = No Error; 1 = Short
Circuit Error
396, 425, 454, 483, 512, 541
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] Presence State (Scaling)
0-100%
397, 426, 455, 484, 513, 542
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] Presence State (HVAC)
Auto, Comfort, Standby,
Economy, Building
Protection
398, 427, 456, 485, 514, 543
1 Bit
O
C T R - -
DPT_Occupancy
0/1
[Ix] Presence State (Binary)
Binary Value
1 Bit
O
C T R - -
DPT_Ack
0/1
[Ix] Presence: Slave Output
1 = Motion Detected
399, 428, 457, 486, 515, 544
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Ix] Presence Trigger
Binary Value to Trigger the
Presence Detection