Technical Documentation 

© Zennio Avance y Tecnología S.L.            Edition 1                                              Further information 

www.zennio.com

                       

Page 

2

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

    

 

 

 

 

     

 
 
 
 
 
 
 

             

 

 

 

 

 

 

 

 

 

                       

      

 

 

 
 
 
 
 
 
 
 
    

 

 
 
 
 
 

               

 

 
 
 
SAFETY INSTRUCTIONS

 

  Installation should only be performed by qualified electricians following applicable regulations on preventing accidents, as 

required by law 

  Do not connect Mains Voltage (230 V) or any other external voltages to any point of the bus.  

Connecting an external voltage might put the entire KNX system at

 

risk. 

  Make sure during the installation that there is always sufficient insulation between the mains voltage 230V and the bus or 

the extension inputs. 

  Once the device is installed, the output terminal should not be accessible.  

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

Contact type 

Potential Free outputs through bistable relays with tungsten pre-contact. 

Disconnection type 

Micro-disconnection 

Rated current by output 

16(6)A * 250V AC (4000 VA)       

 16(6)A * 30V DC (480W) 

Maximum inrush current  

800A/200

μs (inductive load) 

165A/20ms (resistive load) 

Outputs per common (channel) 

1 individual output 

Different phases connection 

Possibility to connect different phases in adjoining outputs 

Maximum current per block 

40A per block 

Maximum power 

Resistive load 

4000W 

Inductive load 

1500W 

Connection Type 

Terminal block (screw)  

Recommended Cable Section 

0.25 mm² a 4 mm²  

Cable Type 

Stranded or solid wire 

Response Time 

50ms  

Expected life 

Mechanical  

3 million operations (60cpm) 

Electrical  

100.000 cycles (6cpm and resistive load) 

 

WIRING AND ASSEMBLY DIAGRAMS 

Figure 2. Block I wiring examples (from left to right): shutter (channel A) + individual outputs (channel B), 

2 shutter channels (A and B), 4 individual outputs and 2-pipe fan coil with 3-speed fan.

 

Attaching MAXinBOX 16 Plus to DIN rail: 

Removing MAXinBOX 16 Plus from DIN rail: 

Figure 3. MAXinBOX 16 Plus DIN-rail assembly

 