Zennio Linecoupler
Technical Support:
http://zennioenglish.zendesk.com
14
3.2
GENERAL
As shown in Figure 9, this screen contains two parameters, both related to the manual
mode of the device (see section 2.2):
Fallback Time for Manual Operation
: sets the maximum operation time for
the manual mode. Once exceeded, the device will automatically leave manual
mode and return to normal mode. The available values are: 10 minutes, 1
hour (default), 4 hours and 8 hours.
Manual Function
: sets the desired function to be executed by the device
while in the manual mode. The available values are: disabled (no action),
pass all telegrams (default option; the device will not filter/drop any telegram
transferred from one line the other), pass physical telegrams (the device will
not filter/drop physical addresses; in other words, all telegrams destined to
physical addresses will be transmitted while in manual mode; on the other
hand, group telegram filtering will stay the same as in normal mode) and pass
group telegrams (the device will not filter/drop group addresses; in other
words, the group address filter table will stay
disabled
while in manual mode;
on the other hand, physical address filtering will stay the same in normal
mode).
3.3
MAIN LINE
This screen permits parameterising the behaviour of the line coupler regarding the
mainline, that is, when the telegrams are being transferred towards the mainline.
Figure 10
Mainline