Fan
[
disabled/
enabled
]
: enables the “Fan” tab, for advanced configuration of
the fan functions. See section 2.2.2.
TEMPERATURE MEASURED BY THE A/C UNIT
Figure 8.
A/C Gateway. Configuration. Temperature measured by the A/C unit.
Monitoring
[
disabled
/enabled
]:
enables the “
[AC] AC Unit Measured
Temperature
” two-byte object, which provides the value of its internal
temperature sensor, which is used by the AC machine to execute the control
loop. Once enabled, a secondary parameter will show:
Sending Type
[
Variation
/ Periodic / Pe Variation
]: sets whether the
above object should be sent only in case of a change in the value,
periodically in both cases, respectively. The latter two options bring entail
one more parameter:
Period
[
1…3600
][
s
] [
1…
15
…1440
][
min
] [
1…24
][
h
]: sets the cycle time
for the periodic sending.
REFERENCE TEMPERATURE
Figure 9.
A/C Gateway. Configuration. Reference temperature.
External Reference Temperature Object
[
disabled
/enabled
]:
enables the
“
[AC] External Reference Temperature
” 2-Byte object, which provides the
value of an external temperature sensor, which is used by the AC machine as
the reference to execute the control loop.