AUTOMATIC OFF
Figure 9.
AC Gateway. Configuration. Automatic Off.
Automatic Off
[
disabled
/enabled
]:
enables the “
[AC] Automatic Off
” and
the
“[AC] Automatic Off (Status)”
binary objects, which lets performing a
temporary switch-off of the A/C unit or reading the current status This object
will be typically linked to a window sensor or a similar event trigger.
During the temporary switch-off state, KLIC-MITT v2 will still monitor any
control orders being received (setpoint, fan speed, etc.), so they can be
applied once it leaves such state.
Automatic Off Delay
[
1…
60
…3600
][
s
]: sets the time, in seconds, KLIC-
MITT v2 waits before switching the A/C machine off. Any switch-off
order received during the delay will abort the time count. This delay can
be modified at runtime through the object
“[AC] Automatic Off Delay”
.
The sending of the value “0” disables the automatic off functionality.
Note
:
switch-on orders sent to the A/C unit from a wired remote control have a
higher priority than the Auto Off mode.
INITIAL CONFIGURATION
Initial Configuration
:
allows setting the desired initial state that KLIC-MITT
v2 will send the A/C unit after programming or restarting the device:
Default
: the initial state will be the last one KLIC-MITT v2 is aware of.
Custom
: see section 2.2.4.
SCENES
Scenes
[
disabled
/enabled
]:
allows setting up different scenes (up to 5),
consisting each of them in a set of orders to be sent to the A/C unit upon the
reception of scene trigger values through the KNX bus. See section 2.2.5.