Sending Mode for Energy
[
Disabled /
Periodic
/ With Value Change /
Periodic and with Value Change
]: sets the sending mode of consumption,
cost and CO
2
emissions objects. Depending on this selection, some more
parameters will be available:
Figure 13
Phases: Global - Total Register
– Sending Modes
➢
Period
[
10
…255
][
s
] [
1…255
][
min/h
]: sets the period between cyclical
sendings.
➢
Minimum Time Between Sendings
[
10
…255
]: sets a minimum period of
time between consecutive sendings.
➢
Minimum Change to Send
[
[
10
…65535][
W·h
] / [
1…65535][kW·h]
]: sets
the minimum value change required to send the
next value.
The communication objects of total registers have the label
“
[Global] [TR]
”.
2.2.2.1.2
Partial registers
Up to two partial registers for global values can be enabled, which store data during a
period of time (for example, a day, a month
…). As the total register, there are partial
registers for consumption, CO
2
emissions and costs.
Two binary object
s “
Reset Partial Register 1
” and “
Reset Partial Register 2
” are
available to reset a partial register anytime (set to zero). Moreover, a
periodic reset
can be configured by parameter.
Every time a partial register is reset, the values of the
immediately previous period
are saved in other communication objects and are sent to the bus. Note that this
sending will take place even if the resending restrictions configured are not met.
Note
:
Partial registers are disabled by default. Please refer to section 2.1 for enabling
them.