Zennio FlatSensato Скачать руководство пользователя страница 21

 

 

 

 

Flat Sensato 

http://www.zennio.com

                                                                      

Technical Support:

 

http://support.zennio.com

 

 

   

 

21 

ANNEX I. DEW POINT THEORY 

Dew  point

  or 

dew  point  temperature

  is  defined  as the  temperature  at which  the  air 

mass is notable to hold more water and, thus, the water begins to condense. 

Therefore,  dew  point  temperature  only  depends  on  the  amount  of  water  in  the  air 

(absolute humidity) as well as the pressure in the mass of air. So that, only modifying 

the air temperature, the dew point temperature does not vary. 

The 

relative humidity

 is, approximately, the ratio of the amount of humidity in the air to 

the  total  amount  of  humidity  the  air  can  hold  (saturation).  On  the  other  hand,  as  air 

temperature increases, the capacity to hold water increases as well. This means that, 

keeping  the  absolute  humidity  constant,  the  relative  humidity  varies  with  the  air 

temperature, according to: 

Temperature 

↑, relative humidity ↓ 

Temperature 

↓, relative humidity ↑ 

For  this  reason,  it  can  be  understood  that  relative  humidity  relates  the  current 

temperature  of  the  air  to  the  absolute  humidity  of  the  air,  and  hence  the  dew  point 

temperature.  In  such  a way,  an  approximation  of  the  dew  point  temperature  could  be 

known by lowering the air temperature until a relative humidity of 100% was obtained, 

which is known as the saturation point. 

An approximation of the ratio between the dew point temperature and the temperature 

of the air can be represented according to the following formula: 

𝑇

𝐷𝑃

= 𝑇

𝑎𝑖𝑟

+ 35 log (𝑅𝐻 100

)

 

 

 

 

Содержание FlatSensato

Страница 1: ...FlatSensato KNX Humidity and Temperature sensor for flush mounting ZS FSEN USER MANUAL Application Program Version 1 0 User Manual Version 1 0 _a www zennio com...

Страница 2: ...o 3 1 2 Installation 4 2 Configuration 6 2 1 General 6 2 2 Temperature 8 2 3 Humidity 11 2 4 Dew Point 14 2 5 Notification LED 16 2 5 1 Configuration 16 2 6 Inputs 18 2 6 1 Binary Inputs 19 2 6 2 Temp...

Страница 3: ...e and condensation The most outstanding features and functions of the device are Measurement of dry air temperature Measurement of relative air humidity indoor Measurement of dew point temperature Ala...

Страница 4: ...of the device Once the input terminal and the KNX terminal are connected the device can be easily mounted on the metallic plate by the action of the fixing clips Finally it is advisable to check that...

Страница 5: ...mming Mode After a short press the programming LED 4 will light in red Note that if this button is held while plugging the device into the KNX bus the device will enter the Safe Mode The LED will then...

Страница 6: ...isables the Inputs tab in the tree on the left depending on whether the device will or will not be connected any external accessories See section 2 6 for details Logic Functions enables or disables th...

Страница 7: ...eriodically with value 1 to notify that the device is still working still alive Figure 4 Heartbeat Periodical Alive Notification Note The first sending after download or bus failure takes place with a...

Страница 8: ...ation Temperature Sensor Calibration defines an offset to be applied to the measurement received from the probe to correct deviations due to external factors The offset should be in the range 50 50 te...

Страница 9: ...at alarm has been triggered the no alarm will not be sent until the current temperature is lower than that T minus the hysteresis After that if the current temperature reaches T again the alarm will b...

Страница 10: ...Flat Sensato http www zennio com Technical Support http support zennio com 10 Overheating Temp Overcooling Temp Hysteresis The three of them are analogous to those already explained separately...

Страница 11: ...iguration Humidity Sensor Calibration defines an offset to be applied to the measurement received from the probe to correct deviations due to external factors The offset should be in the range 12 12 t...

Страница 12: ...s fluctuating around the limit H once the alarm has been triggered the no alarm will not be sent until the current humidity is lower than that H minus the hysteresis After that if the current humidity...

Страница 13: ...ysteresis After that if the current humidity reaches H again the alarm will be re sent Low Humidity and High Humidity high humidity and low humidity alarms are enabled The following three parameters w...

Страница 14: ...ime the value of the current dew point temperature should be sent to the bus through Dew Dew Point Temperature in the range 0 255 tens of second The value 0 leaves this periodical sending disabled Sen...

Страница 15: ...egree the default is 20 tenths of a degree around the dew point This dead band prevents the device from sending the condensation alarm and no alarm over and over when it keeps fluctuating around the l...

Страница 16: ...default threshold values Figure 8 Default colors of Notification LED ETS PARAMETERISATION After enabling Notification LED see section 2 1 a new tab will be incorporated into the tree on the left The p...

Страница 17: ...e 10 Notification LED Green and Yellow The threshold values should be set from highest to lowest from top to bottom If this indication is not met default values will be taken In addition an alert mess...

Страница 18: ...on detector models ZN1IO DETEC P and ZN1IO DETEC X from Zennio Important older models of the Zennio motion detector e g ZN1IO DETEC and ZN1IO DETEC N will not work properly with Flat Sensato ETS PARAM...

Страница 19: ...f Flat Sensato Please refer to the Motion Detector user manual available in the Flat Sensato product section at the Zennio website www zennio com Notes The ZN1IO DETEC P motion detector is compatible...

Страница 20: ...xecution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after ex...

Страница 21: ...d saturation On the other hand as air temperature increases the capacity to hold water increases as well This means that keeping the absolute humidity constant the relative humidity varies with the ai...

Страница 22: ...y 0 No Alarm 1 Alarm 10 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 Dew Surface Temperature Input Surface Temperature Value 11 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 Dew Dew Point Temperatu...

Страница 23: ...n 1 Bit C T DPT_Switch 0 1 Ix Short Press Light Off Sending of 0 Off 1 Bit I C T W DPT_Switch 0 1 Ix Short Press Light On Off Switching 0 1 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Run...

Страница 24: ...t C T DPT_Step 0 1 Ix Long Press Stop Step Down Shutter Sending of 1 Stop Step Down 1 Bit C T DPT_Step 0 1 Ix Long Press Stop Step Shutter Switched Switching of 0 1 Stop Step Up Down 4 Bit C T DPT_Con...

Страница 25: ...Alarm 0 1 Ix Overcooling 0 No Alarm 1 Alarm 28 32 1 Bit O C T R DPT_Alarm 0 1 Ix Overheating 0 No Alarm 1 Alarm 29 33 1 Bit O C T R DPT_Alarm 0 1 Ix Probe Error 0 No Alarm 1 Alarm 34 1 Byte I C W DPT_...

Страница 26: ...5 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 1 Bit I C W DPT_Bool 0 1 LF 1 bit Data Entry x Binary Data Entry 0 1 126 127 128 1...

Страница 27: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: