2.1
Ventilation for All Models
Proper air circulation must be provided for all Boiling and Chilled models. The system will operate correctly
only if the recommended air gaps are achieved during Installation. The minimum requirement is for a 50mm air
gap either side and 300mm above of the undersink unit.
It is important that the 4mm door buffers (For all installations ) are fitted to the inside edge of the
cupboard door to allow suficient air circulation inside the cupboard. (See the diagram below). Under normal
circumstances, these buffers are sufficient for residential models.
IMPORTANT:
See section 4 for clearances.
When installing air flow ducts, the following tools will be required:
•
Jigsaw and 12mm drill
•
Keyhole or Wall Board saw.
Section 2
Ventilation
4mm Buffer
Pad to ensure
ventilation gap
Min 300mm