background image

 

 

 

3.1.3 DISPLAY INDICATIONS 

The controller is capable of recognizing certain types of anomalies in the drying circuit. In such cases, a message will blink on the 
display, alternated to the current dew point value. 

 

MESSAGE 

(BLINKING) 

CAUSE OUTPUTS ACTIONS 

HtA 

High dew point value 

(delayed alarm) 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output ON 
Drain cycle standard 

Resettable by switching off the 
dryer.  
If problem persists call your local 
ZEKS distributor. 

Ht2 

Very high dew point value 

(immediate alarm) 

PF1 
PF2 

Interruption or short circuit on the 

PTC probe input line 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output OFF 
Drain cycle standard 

Resettable by switching off the 
dryer. May require replacing the 
faulty probe. 
If problem persists call your local 
ZEKS distributor. 

ESA 

The automatic Energy saving 

mode activated due to low load 

Alarm output OFF 
Refrig. Compressor output OFF 
Fan output OFF 
Drain cycle standard 

No action necessary. 
Automatic Reset 

ES2 

ASt 

Activated after repeated alarms 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output ON 
Drain cycle standard 

Call your local ZEKS distributor. 

PCd 

Glycol circuit malfunction 

Alarm output ON 
Refrig. Compressor output ON 
Fan output ON 
Drain cycle standard 

Resettable by switching off the 
dryer. See troubleshooting section. 
If problem persists call your local 
ZEKS distributor.

 

Cnd 

High compressor output 

temperature 

Alarm output ON 
Refrig. Compressor output OFF 
Fan output ON 
Drain cycle standard 

No action necessary. 
Automatic Reset 

 

Note: PF1 has priority on all other messages. 

 

3.1.4 REMOTE SIGNALING ALARM 

 

 

 

 

The dryer control board is equipped with a terminal block for a remote alarm signal.  
Proceed as follows to activate a remote alarm output: 
 

1.  Disconnect the dryer from electrical power supply, remove cover and left side panel. 
2.  Connect the alarm circuit to the terminal block (See PIC.2). 

3. 

Replace cover, left side panel and reconnect power.

 

Alarm Output electric features: 

12V DC - 40mA on alarm,  

0V on normal conditions.

 

PIC.2

 

 

Activation of the above function is at the User’s discretion. The User will purchase all necessary 
installation material. Any operation which needs access to the dryer must be carried out by qualified 
personnel. 

 
 

 

Содержание HeatSink HSH Series

Страница 1: ...hnical Manual Ensure that this Technical Manual is not removed permanently from the machine TECHNICAL MANUAL HeatSink Cycling Refrigerated Compressed Air Dryers HSH Models 10 125 SCFM ZEKS Compressed...

Страница 2: ...rge parameters programming 6 3 1 3 Display Indications 7 3 1 4 Remote signalling alarm 7 3 2 Before start up 8 3 3 Start up 8 4 MAINTENANCE TROUBLESHOOTING AND DISMANTLING 4 1 Maintenance 8 4 2 Troubl...

Страница 3: ...or others without ZEKS s prior written approval The effects of corrosion erosion and normal wear and tear are specifically excluded Performance warranties are limited to those specifically stated wit...

Страница 4: ...c shock by providing an alternate lower resistence route for the electrical current Ground must be established with a bare grounding wire sized according to the voltage and minimum branch circuit requ...

Страница 5: ...sure to leave sufficient clearance 20 inches 500 mm around the dryer to allow adequate cooling of the machine and for maintenance and or control operations The incoming air must be free of smoke or f...

Страница 6: ...nergy and avoid heat exchanger freezing This situation can happen when ambient temperature is low and there is no compressed air load Energy Saving System A patented 3 layer air glycol freon heat exch...

Страница 7: ...NOTE when the controller is in the OFF position some parts of the dryer may still be energized Therefore for safety purposes disconnect the electrical power before performing any maintenance operatio...

Страница 8: ...rms Alarm output ON Refrig Compressor output OFF Fan output ON Drain cycle standard Call your local ZEKS distributor PCd Glycol circuit malfunction Alarm output ON Refrig Compressor output ON Fan outp...

Страница 9: ...if the condensate drain is working properly 9 Check if all connecting pipes are properly tightened and fixed Before disconnecting the dryer from electrical power supply use ON OFF button on controlle...

Страница 10: ...an or replace the drainage solenoid valve if clogged jammed Check the C8 and C9 parameters of the electronic control board if the trouble persists replace it No loss condensate drain is not functionin...

Страница 11: ...vaporator Check the probe if the trouble persists replace it Check the electronic control board if the trouble persists replace it Contact ZEKS to check the gas charge Clog Check if the compressed air...

Страница 12: ...the relevant packaging in compliance with the local rules and regulations Pay particular attention to the refrigerant as it contains part of the refrigeration compressor lubricating oil Always contact...

Страница 13: ...12 Flow Diagram HeatSink HSH Dryers 10 125 SCFM...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: