background image

 

 
 
 
 
 

1. GENERAL INFORMATION 

 

1.1 FUNCTIONAL DESCRIPTION 

ZEKS refrigerated air dryers remove moisture from compressed air. Moisture is detrimental to pneumatically operated 
appliances, controls, instruments, machinery and tools.  

Hot compressed air enters the patented aluminum heat exchanger where it is cooled down to the dew point temperature in 

two different stages: In the first stage, the precooler/reheater makes use of the colder compressed air exiting counterflow from 
the condensate separator to cool the inlet air.  In the second stage, the compressed air  temperature is further reduced as it 
passes through the refrigerant-to-air and glycol chiller.  During these two stages almost all the oil and water vapor contained in 
the compressed air are condensed to liquid and successively separated from it in the condensate separator, then drained out by 
the automatic drain.  The cold compressed air then re-enters the precooler/reheater where it is heated before exiting the dryer 
for use. 

When operating at partial loads, the dryer uses the energy previously stored in the gycol circuit, shuts down the compressor 

and substantially saves energy and costs. 

This dryer can be easily installed into various pneumatic systems in which dry air is required or desired. Please refer to Start 

Up chapter for complete operating details. 

 

 

 

The dryer comes provided with all the control, safety and adjustment devices, therefore no auxiliary devices are 
needed. 
Improper grounding can result in electrical shock and can cause severe injury or death. 
This product must be connected to a grounded, dedicated service, permanent wiring system . 
All grounding must be performed by a qualified electrician and comply with national and local electrical codes. 
In the event of an electrical short circuit, grounding reduces the risk of electric shock by providing an alternate, lower 
resistence, route for the electrical current. 
Ground must be established with a bare grounding wire sized according to the voltage and minimum branch circuit 
requirements.  
Ensure good bare metal contact at all grounding connection points, and ensure all connections are clean and tight.  
Check grounding connections after initial installation and periodically thereafter to ensure good contact and 
continuity has been maintained. 
Check with a qualified electrician or service technician if the grounding instructions are not completely understood, or 
if in doubt as to whether the product is properly grounded. 

 
 
 

1.2 USE OF THE MACHINE IN SAFE CONDITIONS 

Because an air dryer is pressurized and contains rotating parts, the same precautions should be observed as with any 

piece of machinery of this type where carelessness in operation or maintenance could be hazardous to personnel. In 
addition to obvious safety rules that should be followed with this type of machinery, safety precautions as listed below 
must be observed. 

 

 

 

 

 

1.  Only qualified personnel shall be permitted to adjust, perform maintenance or repair this air dryer. 
2.  Read all instructions completely before operating unit. 
3.  Pull main electrical disconnect switch and disconnect any separate control lines, if used, before 

attempting to work or perform maintenance on the unit. 

4.  Do not attempt to service any part while machine is in an operational mode. 
5.  Do not attempt to remove any parts without first relieving the entire air system of pressure. 
6.  Do not attempt to remove any part of the refrigeration system without removing and containing 

refrigerant in accordance with the EPA and local regulations. 

7.  Remove any trace of spilled surface fluids before connecting the dryer to electrical power. 
8.  Do not operate the dryer at pressures in excess of its rating. 
9.  Do not operate the dryer without guards, shields and screen in place. 
10.  Inspect unit daily to observe and correct any unsafe operating conditions. 

 

 

 

Содержание HeatSink HSH Series

Страница 1: ...hnical Manual Ensure that this Technical Manual is not removed permanently from the machine TECHNICAL MANUAL HeatSink Cycling Refrigerated Compressed Air Dryers HSH Models 10 125 SCFM ZEKS Compressed...

Страница 2: ...rge parameters programming 6 3 1 3 Display Indications 7 3 1 4 Remote signalling alarm 7 3 2 Before start up 8 3 3 Start up 8 4 MAINTENANCE TROUBLESHOOTING AND DISMANTLING 4 1 Maintenance 8 4 2 Troubl...

Страница 3: ...or others without ZEKS s prior written approval The effects of corrosion erosion and normal wear and tear are specifically excluded Performance warranties are limited to those specifically stated wit...

Страница 4: ...c shock by providing an alternate lower resistence route for the electrical current Ground must be established with a bare grounding wire sized according to the voltage and minimum branch circuit requ...

Страница 5: ...sure to leave sufficient clearance 20 inches 500 mm around the dryer to allow adequate cooling of the machine and for maintenance and or control operations The incoming air must be free of smoke or f...

Страница 6: ...nergy and avoid heat exchanger freezing This situation can happen when ambient temperature is low and there is no compressed air load Energy Saving System A patented 3 layer air glycol freon heat exch...

Страница 7: ...NOTE when the controller is in the OFF position some parts of the dryer may still be energized Therefore for safety purposes disconnect the electrical power before performing any maintenance operatio...

Страница 8: ...rms Alarm output ON Refrig Compressor output OFF Fan output ON Drain cycle standard Call your local ZEKS distributor PCd Glycol circuit malfunction Alarm output ON Refrig Compressor output ON Fan outp...

Страница 9: ...if the condensate drain is working properly 9 Check if all connecting pipes are properly tightened and fixed Before disconnecting the dryer from electrical power supply use ON OFF button on controlle...

Страница 10: ...an or replace the drainage solenoid valve if clogged jammed Check the C8 and C9 parameters of the electronic control board if the trouble persists replace it No loss condensate drain is not functionin...

Страница 11: ...vaporator Check the probe if the trouble persists replace it Check the electronic control board if the trouble persists replace it Contact ZEKS to check the gas charge Clog Check if the compressed air...

Страница 12: ...the relevant packaging in compliance with the local rules and regulations Pay particular attention to the refrigerant as it contains part of the refrigeration compressor lubricating oil Always contact...

Страница 13: ...12 Flow Diagram HeatSink HSH Dryers 10 125 SCFM...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: