Table B
Motor Type
02
03
04
06
08
10
12
HP
PSC
Standard
1/30
1/30
1/25
1/15
1/30, 1/15
(2) 1/15
(2) 1/15
High-Static
1/12
1/12
1/10
1/7
1/12, 1/7
(2) 1/7
(2) 1/7
ECM
Standard
1/4
1/4
1/4
1/4
(2) 1/4
(2) 1/4
(2) 1/4
High-Static
1/4
1/4
1/4
1/4
(2) 1/4
(2) 1/4
(2) 1/4
RPM High
PSC
Standard
895
995
900
1150
1150
1250
1200
High-Static
1505
1510
1550
1550
1550
1550
1550
ECM
Standard
1050
1025
920
1120
1150
1250
1200
High-Static
1550
1550
1550
1550
1550
1550
1550
RPM Medium
PSC
Standard
833
754
720
900
900
860
950
High-Static
1390
1320
1320
1320
1320
1320
1320
ECM
Standard
875
700
720
870
900
850
950
High-Static
1320
1320
1320
1320
1320
1320
1320
RPM Low
PSC
Standard
620
575
530
710
625
650
550
High-Static
1300
1200
1000
1000
1000
1000
1000
ECM
Standard
750
600
530
685
625
640
550
High-Static
1000
1000
1000
1000
1000
1000
1000
Motor FLA 120V
PSC
Standard
0.60
0.60
0.68
1.13
1.73
2.26
2.26
High-Static
1.05
1.05
1.2
1.7
2.8
3.4
3.4
ECM
Standard
0.92
0.84
1.12
1.70
2.85
3.04
3.58
Power Input:
Watts 120V
PSC
Standard
57
61
75
130
200
240
250
High-Static
117
120
130
180
325
368
368
ECM
Standard
38
38
45
80
125
147
157
Electrical data
Notes:
Maximum circuit ampacity (MCA) =
1.25 x (FLA motor 1 + FLA motor 2 + FLA electric heat)
Maximum overcurrent protection (MOP) =
(2.25 x FLA motor 1) + FLA motor 2 + FLA electric heat
If the calculated MOP is within 10% of the next smaller available fuse size,
that fuse size shall be used. If not, the next larger fuse size above the
calulated MOP must be used.
If the selected MOP is smaller than the MCA, the selected MOP must be
increased to the next larger available fuse size above the MCA.
If the MOP is less than 15, it shall be rounded up to 15 amps. This is the
minimum fuse or circuit breaker permitted by code.
EC motor nameplate amperage indicates the motor hardware peak
amperage while the motor full load amperage (FLA) is limited by the motor’s
factory programmed operating range, programmed specifically for each unit
size. The programmed operating range is generally only a portion of the
motor hardware full potential resulting in the motor FLA being lower than
the nameplate FLA. Motor FLA will be reflected on the Cabinet Unit Heater
serial tag and should be used when sizing building electrical requirements.