Installing your towel radiator and its remote control
39
10/2017
EN
38
40016514
2. Installing your towel radiator and its
remote control
2.1 Warnings
The flexible cable supplied with your appliance is
designed to be connected to the mains via a junction box
that must be placed behind the appliance, with no need for
a plug.
In a kitchen or bathroom, the junction box must be
positioned at least 25 cm from the floor.
The appliance must be installed as described in this
document and in accordance with the applicable European
and French standards, including CEI 60364.7.701 and NF
C15-100, as well as the rules of good professional practice.
For other countries (apart from France), the appliance
must be installed in accordance with standards in force and
with rules of good professional practice in the country of use.
IMPOrTANT
The example shown only concerns a
bathtub. For other bathroom fixtures, please consult your
installer.
IMPOrTANT
The system must be fitted with an
omnipolar circuit-breaker with a minimum contact
opening of 3mm
.
Volume 0
Volume 1
Volume 2
0.60 m
2
.2
5
m
IMPOrTANT
Always turn off the electricity supply
(circuit-b pilot wire) before making any connec-
tions.
To ensure your system is safe (see figure
①
):
- ensure that an area of at least 50 cm in front of the
appliance is clear of objects which might hinder air
circulation (furniture, chairs, etc.),
- ensure that the bottom of the appliance is positioned at
least 23 cm above the floor,
- leave at least 10 cm between the top of the appliance
and any shelf,
- use mounting screws suitable for your wall,
- do not expose the radiator to intense or prolonged
humidity.
IMPOrTANT
This radiator must never be installed with
its blower at the top (see figure
②
).
NOTE:
When installing your towel radiator, make
sure it is not resting on the blower or on its
infra-red receiver (see figure
③
).
③
②
≥100
mm
≥500
mm
≥100
mm
≥
230mm