EN 17
Menu P7
Reading malfunctions (and system information)
(Malfunction) information values
Submenu description
Minimum Maximum Factory reset
P70
Current software version.
Software version number
(without "v")
P71
Most recent malfunction.
Code in accordance with alarm
and malfunction alert
P72
Second most recent malfunction
Code in accordance with alarm
and malfunction alert
P73
Third most recent malfunction
Code in accordance with alarm
and malfunction alert
P74
Resetting a malfunction
• Set the value to ‘1’ and press “ OK” or “
”.
0
1
(= activate)
0
P75
Factory reset
• Set the value to ‘1’ and press
“ OK” or “
”.
All original software settings are restored follow-
ing a factory reset.
0
1
(= activate)
0
Note:
After a general reset, the ventilation unit will ask you to reset the “nL / HL” (see
P56) and “Li / Re” (see P57) settings.
After a general reset, all settings and programmes must be checked and set to
the correct values where necessary.
P76
Self-testing
the ventilation unit
.
0
1
(= activate)
0
Note:
• The LEDs on the display of the ventilation unit will start flashing.
• The ventilation unit will start running at its maximum speed (rPM).
• The bypass valve of the ventilation unit will open and close.
• The frost-free element valve of the ventilation unit will open and close once the bypass
valve is closed (if a frost-free element is registered).
P77
resetting filter dirty counter.
0
1
(= activate)
0
Note:
This resets the counter that triggers a dirty filter alert on
the ventilation unit
. This allows the
filter to be cleaned or replaced before the dirty filter alert appears.