background image

 

15

5.2 Exterior  mounting 

The dimensions refer to the above-mentioned standard unit, version with cellular filter (PF). 
For these dimensions, a post-heater (POH) can be used as standard. 

Type 

L

[mm]

B

[mm]

H

[mm]

Air connection

[mm]

Weight

[kg]

ComfoAir XL 800 

1750

700

1168

525 x 395

335-385

ComfoAir XL 1500

1750

1050

1168

875 x 395

420-460

ComfoAir XL 2200

2514

700

1500

612 x 612

560-750

ComfoAir XL 3300

2514

1050

1500

962 x 612

730-920

ComfoAir XL 4400

2514

1400

1500

1312 x 612

900-1090

ComfoAir XL 6000

2514

1750

1500

1662 x 612

1070-1280

The following dimensions refer to the additional length of the optional components.

Option 

Additional length

[mm]

Bag filter (BF) or pre-heater (PRH)* or empty section

350

Cooler (CL) or empty section

350

*  ComfoAir XL 800 and ComfoAir XL 1500 do not require an additional length for the PRH;  

a pre-heater (PRH) fits as standard here.

Содержание ComfoAir XL Series

Страница 1: ...Cooling Filtering Heating Ventilation Technical documentation ComfoAir XL 800 6000 The latest generation of ventilation units with heat recovery...

Страница 2: ...d be delighted to support you Detailed recommendations based on a special operating point with price details Support in the project draft and implementation Instructions on ventilation systems Telepho...

Страница 3: ...s 8 2 9 Design 9 3 Control unit 10 3 1 Controller 10 3 2 Supply 10 4 Quick selection 11 4 1 Coding 11 4 2 Selection schematic 11 4 3 Selection chart 12 5 Dimensions and weight 14 5 1 Indoor installati...

Страница 4: ...fic fan output is less than 0 34 W m h 1 3 ComfoAir XL series and options The ComfoAir XL series is available in a variety of versions and with numerous options The focus was placed on the smallest po...

Страница 5: ...5 1 4 Block diagram Filter Heater Cooler Heat exchanger Fan Temperature sensor Bypass Flap ODA Outside air EHA Exhaust air ETA Extract air SUP Supply air...

Страница 6: ...han 3 An overview of the specifications is provided below Feature Class Mechanical strength 2A Internal leak at 400 Pa 3 of the nominal volume External leak at 400 Pa 3 of the nominal volume Thermal i...

Страница 7: ...condensate that forms on the cooler The siphon can be kept frost free by using an insulated ribbon heating element The contact for supply and control can be set in the software 2 5 Bypass ComfoAir XL...

Страница 8: ...heat exchanger and can be used as a frost protection system The preheater is calculated on the basis of the water glycol medium to prevent the battery from freezing Post heater The post heater increas...

Страница 9: ...Metal support frame ComfoAir XL is equipped with the following components as standard for mounting outdoors G Support frame made of galvanised metal H Coated metallic cover I Two droplet catchers Opt...

Страница 10: ...elay Generation of summer night cooling via digital input Compatible with fire alarm system via digital input Summer night cooling activation via an external signal Frost protection for the high perfo...

Страница 11: ...r BF Bag filter I Indoor installation O Outdoor installation B Bypass open closed BM Bypass modulating R Right handed version L Left handed version CFE Counterflow plate heat exchanger Product type de...

Страница 12: ...ng to NEN 5138 2004 COLD RECOVERY Outside air conditions C RH Extract air conditions C RH Temperature efficiency perceptible performance PREHEATER Air volume m s Air volume m h Temperature distributio...

Страница 13: ...1 79 8 79 6 79 8 79 6 28 60 28 60 28 60 28 60 28 60 28 60 24 55 24 55 24 55 24 55 24 55 24 55 79 3 79 6 79 2 79 2 78 9 79 2 0 22 0 42 0 56 0 92 1 22 1 67 800 1500 2200 3300 4400 6000 60 40 60 40 60 40...

Страница 14: ...68 875 x 395 310 340 ComfoAir XL 2200 2514 700 1500 612 x 612 450 600 ComfoAir XL 3300 2514 1050 1500 962 x 612 600 750 ComfoAir XL 4400 2514 1400 1500 1312 x 612 750 900 ComfoAir XL 6000 2514 1750 15...

Страница 15: ...ComfoAir XL 2200 2514 700 1500 612 x 612 560 750 ComfoAir XL 3300 2514 1050 1500 962 x 612 730 920 ComfoAir XL 4400 2514 1400 1500 1312 x 612 900 1090 ComfoAir XL 6000 2514 1750 1500 1662 x 612 1070...

Страница 16: ...6 6 Technical data 6 1 Technical data ComfoAir XL 800 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 17: ...m3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 363 52 56 8 46 2 37 5 38 0 31 8 22 4 45 2 625 150 60 6 52 4 43 0 42 6 36 1 27 8 49 3 818 260 64 9 59 3 49 2 47 9 40...

Страница 18: ...18 6 2 Technical data ComfoAir XL 1500 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 19: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 881 86 61 0 59 5 55 2 49 6 45 9 37 6 57 2 1119 139 61 8 61 7 57 4 51 5 47 6 39 6 59 3 1528 260 63 7 66 6 62 3 55 8 51...

Страница 20: ...20 6 3 Technical data ComfoAir XL 2200 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 21: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 986 50 60 1 63 6 49 5 49 3 41 4 33 8 57 2 1498 116 65 3 66 0 59 7 58 0 49 4 42 2 63 3 2187 247 72 4 69 3 73 4 69 6 60...

Страница 22: ...22 6 4 Technical data ComfoAir XL 3300 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 23: ...h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 1788 73 64 5 64 6 59 3 49 2 46 6 38 3 60 2 2623 158 66 4 72 4 67 4 56 5 53 0 45 4 68 3 3334 255 68 0 79 1 74 4 62 7 58...

Страница 24: ...24 6 5 Technical data ComfoAir XL 4400 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 25: ...h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 2228 64 65 4 59 1 53 4 49 9 47 3 37 2 57 2 3261 137 74 2 77 7 67 8 64 8 63 1 55 9 73 3 4453 256 75 3 83 7 72 6 69 9 69...

Страница 26: ...26 6 6 Technical data ComfoAir XL 6000 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Страница 27: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 3105 67 70 6 72 0 60 4 56 6 52 5 42 2 66 2 4592 146 75 4 78 8 68 2 65 1 61 2 51 9 73 3 5899 242 79 6 85 4 75 1 72 8 6...

Страница 28: ...basis of the ventilation requirement in the room If the CO2 concentration is high the ventilation stage is increased automatically If the CO2 concentration is low the ventilation stage is reduced aut...

Страница 29: ...bH Sales International Almweg 34 77933 Lahr Germany T 49 7821 586 392 F 49 7821 586 406 sales international zehndergroup com www international zehnder systems com Z_SI_V0414_CSY_DAS_ComfoAirXL en subj...

Отзывы: