INSTALLATION INSTRUCTIONS

X-XX UL

69-0771B

ST9103A

Electronic Fan Timer

APPLICATION

The ST9103A Electronic Fan Timer integrates control of all
burner and circulator fan operations in an oil furnace. This
control is the central wiring point for most of the electrical
components in the furnace. The basic purposes of the
ST9103A are to monitor the thermostat for heat, cool, and fan
demands and run the oil burner primary control and up to a
two-speed circulating fan as required. The ST9103A also
monitors a limit switch string, which energizes the circulating
fan whenever the limit switch opens.

Electronic air cleaner and humidifier convenience terminal
connections may be provided as an option. A means for
operating continuous indoor air circulation is also available as
an option.

SPECIFICATIONS

Electrical Ratings:

Power Requirements:

Voltage: 18-30 Vac, 50/60 Hz.
Current: 4 VA at 24 Vac.

Contact Ratings:

Circulating Fan: 15A Full Load, 30A  Locked Rotor at
115 Vac (includes optional EAC load).

On/Off Delay Settings:

Delay On: 30 seconds, fixed.
Delay Off: 60, 90, 120, 150 seconds, field-adjustable.
Timing Tolerance: larger of 

±

20% or 5 seconds.

Envrionmental Ratings:

Temperature: -40 to +150

°

 F [-40

°

 to +66

°

 C].

Humidity: 95% maximun, noncondensing.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous
condition.

2. Check the ratings and specifications given in the

Instructions and on the product to assure the product is
suitable for your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out the product

operation as provided in these instructions.

CAUTION

Disconnect power supply before wiring to prevent
electrical shock or equipment damage.

Location and Mounting

The ST9103A is mounted in the appliance wiring
compartment using four No. 6 screws (obtained locally)
through standoffs on the corners of the board.

Wiring

All wiring must comply with local codes and ordinances.
Disconnect power before making wiring connections. Refer to
Fig. 1 for standard wiring connections. Refer to Fig. 2 for an
internal schematic.

Setting the Heat Fan Off Delay Switches

Set the heat fan off delay switches to either 60, 90, 120, or
150 seconds, as shown in Fig. 3. The off delay time starts
when the burner motor is de-energized at the end of a
thermostat call for heat.

CHECKOUT

Assure the system operates properly by operating the system
through at least one complete heating cycle and cooling
cycle, if applicable. Troubleshoot by checking for appropriate
voltages at the ST9103A terminals controlling the burner
motor and heat and cool speed circulating fan. The ST9103A
schematic shows internal switching to clarify operation and
assist in troubleshooting.  See Fig. 2.

Содержание ST9103A

Страница 1: ...1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings and specifications given in the Instructions and on the product to assure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out the product operation as provided in these...

Страница 2: ...1 C O O L C O N T E A C B U R N E R UNUSED MOTOR 1 2 3 4 5 6 7 BURNER MOTOR ST9103 L1 L2 ORANGE T1 T2 BLACK WHITE R8991 OIL PRIMARY CONTROL FLAME DETECTOR CAD CELL 1 INTERLOCK FUSE LIMIT CONTROL H E A T 3 1 2 1 DENOTES STANDARD TERMINAL DENOTES OPTIONAL TERMINAL 1 L2 N L1 H TO 120 VAC POWER SUPPLY H U M NOTE DENOTES LINE VOLTAGE CONNECTIONS DENOTES LOW VOLTAGE CONNECTIONS ...

Страница 3: ... CIRCUIT BOARD WIRING M5552 ELECTRONIC AIR CLEANER OPTIONAL TO 120 VAC POWER SUPPLY R8991 LIMIT SENSOR CIRCULATION BLOWER K1 K2 R8991 CONTROL K3 MED HIGH LOW FUSE INTERLOCK S2 N3 K2 HEAT K1 CONSTANT MED HIGH N1 LIMIT CN6 1 1 CN6 2 CN6 4 L1 L2 CN6 7 T1 T2 R8891 CN6 6 CN6 3 X 24 VAC 120 VAC S1 BURNER MOTOR HUMIDIFIER OPTIONAL ACCESSORY OPTIONAL S3 CN6 8 CN6 5 N7 N4 N6 HUM 1 DENOTES OPTIONAL CONNECTI...

Страница 4: ...y timing begins When timing is complete the circulating fan is de energized ST9103A returns to standby mode oil primary control and circulating fan are off Burner fails to light Oil primary control locks out within lockout timing timing depends on oil primary control Burner motor is de energized If heat fan has started it continues through the selected delay off period Established flame fails Burn...

Страница 5: ... connections Oil primary control is energized initiating burner light off Continuous circulating fan is connected Optional connectors are available for separate circulating fan speed tap Circulating fan is energized at low speed when there is no call for heat cool or fan If fan operation is required by a call for heat cool or fan the ST9103A switches off the continuous fan speed tap before energiz...

Страница 6: ...97 Printed in U S A Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Helping You Control Your World ...

Страница 7: ... Avant d installer ce produit 1 Bien lire les instructions Ne pas les suivre pourrait endommager le produit et constituer un danger 2 Vérifier les caractéristiques spécifiées dans la fiche technique et sur le produit afin de s assurer que le produit convient à l application choisie 3 L installateur doit être un technicien d expérience ayant reçu la formation appropriée 4 Une fois l installation te...

Страница 8: ...9103 L1 L2 ORANGE T1 T2 NOIR BLANC RÉGULATEUR PRIMAIRE DE MAZOUT R8991 DÉTECTEUR DE FLAMME CELLULE AU CADMIUM 1 VERROUILLAGE FUSIBLE INTERRUPTEUR DE FIN DE COURSE 3 1 2 1 BORNE STANDARD BORNE FACULTATIVE 1 L2 N L1 H H U M NOTE RACCORDEMENT TENSION SECTEUR RACCORDEMENT BASSE TENSION BASSE MOYENNE BASSE MOYENNE ÉLEVÉE ÉLEVÉE 120 V C A 24 V C A SOUS TENSION NEUTRE VERS ALIMENTATION 120 V C A INUTILIS...

Страница 9: ...TEUR DU LIMITEUR R8991 VENTILATEUR DE CIRCULATION D AIR K1 K2 R8991 CONTROL K3 MOYENNE ÉLEVÉE BASSE FUSIBLE VERROUILLAGE S2 N3 K2 CHAUFFAGE K1 CONTINUE MOYENNE ÉLEVÉE N1 INTERRUPTEUR DE FIN DE COURSE CN6 1 1 CN6 2 CN6 4 L1 L2 CN6 7 T1 T2 R8891 CN6 6 CN6 3 X 24 V C A 120 V C A S1 MOTEUR DU BRÛLEUR HUMIDIFICATEUR FACULTATIF ACCESSOIRE FACULTATIF S3 CN6 8 CN6 5 N7 N4 N6 HUM 1 CONNEXIONS COMPOSANTS ET...

Страница 10: ...ation le ventilateur de circulation d air est sous tension et l air chaud circule dans les pièces Fin de la commande de l appel de chaleur du thermostat Borne W hors tension Le régulateur primaire est hors tension et met fin au cycle de chauffage La temporisation d arrêt du ventilateur de chauffage commence À la fin de la temporisation le ventilateur de circulation d air est hors tension Le ST9103...

Страница 11: ... ou de ventilation le ventilateur de circulation passe du régime de chauffage à celui de refroidissement Le câble de l interrupteur de fin de course se ferme Le ST9103A commande le début de la temporisation d arrêt du ventilateur de chauffage À la fin de la temporisation choisie le ventilateur de circulation s arrête Le ST9103A referme les contacts T T du régulateur primaire Le régulateur primaire...

Страница 12: ...B G H 3 97 Imprimé aux États Unis Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Pour la ma trise de votre univers ...

Отзывы: