Zehnder Rittling ComfoAir E 350 Скачать руководство пользователя страница 10

10 - EN

2.6 Explanation of VENTILATION SETTINGS 

menu

The building regulations describe how much fresh 
supply air must be provided to each room. The 
VENTILATION SETTINGS must be programmed in such 
a way that the unit can supply the maximum necessary 
volume of fresh air for the entire building. If only HIGH 
SETTING is programmed, the unit will automatically 
set MEDIUM SETTING to 66% of HIGH SETTING, and 
LOW SETTING to 33% of HIGH SETTING. If MEDIUM 
SETTING or LOW SETTING is programmed, this 
automatic link will be lost. To recover the link, all the 
unit's FACTORY SETTINGS must be restored via the 
FACTORY RESET function. 

FACTORY SETTINGS

ComfoAir E

350

HIGH SETTING

315 m

3

/h

MEDIUM SETTING

205 m

3

/h

LOW SETTING

105 m

3

/h

Once the settings screen or valve setup screen is visible, 
the unit switches off all automatic programmes and runs 
on the set value so that all valves can be properly set. 
After touching the screen, you have 60 minutes to set all 
valves. The unit then switches back automatically to the 
normal operating mode and the main screen. Every time 
the screen is touched, the 60-minute timer is reset. If the 
settings screen or valve setup screen is exited manually, 
the unit returns directly to the normal operating mode 
and after 15 minutes without being touched the unit 
returns automatically to the main screen.

2.7 Explanation of REPLACE FILTER warning

The filter warning appears by default 21 days before the 
filters need to be replaced. This gives the user enough 
time to purchase new filters before the dirty filters are 
to be replaced. It is possible to set the alert to appear 
earlier by increasing the number of filter order days in 
the service menu FILTER ALERT. The filters must be 
replaced at least once every 180 days.

2.8 Explanation of ALTITUDE menu

This value compensates for the influence of altitude on 
the air volume. In the “Altitude” menu, the altitude of the 
installation location of the unit must be specified. 

2.9 Explanation of TEMPERATURE menu 

The unit is equipped with 5 temperature sensors. The 
readout of the current value of these sensors appears in 
the TEMPERATURE menu in the sequence given below.

Meaning

OUTDOOR AIR 
TEMPERATURE
(TEMP SENSOR 20)

Outdoor air temperature prior to 
the preheater

EXHAUST AIR TEMPERATURE
(TEMP SENSOR T12)

Exhaust air temperature

EXTRACT AIR TEMPERATURE
(TEMP SENSOR T11)

Extract air temperature

SUPPLY AIR TEMPERATURE
(TEMP SENSOR T22)

Supply air temperature

PREHEATER TEMPERATURE
(TEMP SENSOR T21)

Outdoor air temperature after the 
preheater.

2.10  Explanation of FANS menu

The unit is equipped with 2 fans. The readout of the 
current value of these fans appears in the FANS menu in 
the sequence given below.

Meaning

SUPPLY FAN [RPM]
(FAN 22)

Speed of the supply fan.

EXHAUST FAN [RPM]
(FAN 12)

Speed of the exhaust fan.

SUPPLY FAN [%]
(FAN 22)

Control percentage (fan duty) of 
the supply fan.

EXHAUST FAN [%]
(FAN 12)

Control percentage (fan duty) of 
the exhaust fan.

SUPPLY FAN [m

3

/h]

(FAN 22)

Airflow rate (flow) of the supply 
fan.

EXHAUST FAN [m

3

/h]

(FAN 12)

Airflow rate (flow) of the exhaust 
fan.

10001047667-0619-zw-zw-A4 ComfoAir E 350 GEN2 Service Zehnder-SI_EN.indd   10

11-07-19   13:30

Содержание ComfoAir E 350

Страница 1: ...Cooling Ventilation Filtering Heating ComfoAir E350 Manual for the service engineer 10001047667 0619 zw zw A4 ComfoAir E 350 GEN2 Service Zehnder SI_EN indd 1 11 07 19 13 30...

Страница 2: ...the display on the unit Information given in the Manual for the fitter Fitting conditions Information on transport and unpacking Commissioning procedures Installation procedures Available controls Ava...

Страница 3: ...ns 14 3 1 Service parts 16 3 2 Connection diagram 17 3 3 Dimension sketch 19 4 Maintenance procedures 20 4 1 Procedure for opening the unit 20 4 2 Maintenance of the casing 21 4 3 Maintenance of the h...

Страница 4: ...performance Installation commissioning and maintenance must be carried out by a certified person or company unless stated otherwise If this work is carried out by unauthorised persons it may result i...

Страница 5: ...the menu screen E Icon for activating the comfort temperature menu F Icon for activating the filter replacement menu G Icon for activating the error readout menu H Icon for activating the installer s...

Страница 6: ...TTING EXHAUST AIR TEMPERATURE LOW SETTING EXTRACT AIR TEMPERATURE FANS Readout SUPPLY AIR TEMPERATURE SUPPLY FAN RPM FIREPLACE MODE YES NO PREHEATER TEMPERATURE EXHAUST FAN RPM BALANCE SETTING SERVICE...

Страница 7: ...e heat exchanger are removed To prevent electrically charged parts being touched the power must still be manually disconnected from the unit after setting the SERVICE MODE Once the power is reconnecte...

Страница 8: ...for these valves Adjust the opened valves to the required air flow per room Measure the air flow again at each opened valve using a flow meter Check that the air flow complies with the standard for ea...

Страница 9: ...MENU RF SETTING ACTIVATION ON You now have 10 minutes to register the RF control Set METHOD on the display of the unit to DISCRETE CONTROL MENU SERVICE MENU RF SETTING METHOD DISCRETE CONTROL 4 6 sec...

Страница 10: ...ives the user enough time to purchase new filters before the dirty filters are to be replaced It is possible to set the alert to appear earlier by increasing the number of filter order days in the ser...

Страница 11: ...in frost conditions until deactivation 2 13 Explanation of ANALOGUE 0 10 V menu standard and RF SETTING optional The unit can be controlled with any analogue 0 10 V signal and or an RF signal To ensu...

Страница 12: ...ce ALTITUDE entered incorrectly Filters are dirty Heat exchanger is frozen 2 16 Explanation of RESTORE TO FACTORY SETTINGS menu The factory settings of the unit are permanently saved to the control PC...

Страница 13: ...al Geschwindigkeit Input signal 4 V Setting 1 Input signal between 4 V and 7 V Setting 2 Input signal 7 V Setting 3 What are the P VALUE and the I VALUE for PI Controller Proportional means that the d...

Страница 14: ...Polystyrene General Temperature range during transport and storage 20 C to 50 C Temperature range moved air 15 C to 50 C Temperature range of installation area 8 C is not a range Relative humidity of...

Страница 15: ...15 49 36 34 2 200 50 36 0 42 0 18 53 40 38 3 245 50 46 0 44 0 19 56 42 41 4 250 100 59 0 46 0 24 59 44 43 5 300 100 73 0 47 0 24 62 47 46 6 350 100 90 0 48 0 26 65 49 49 7 250 150 71 0 47 0 28 61 46 4...

Страница 16: ...0 control PCB with display 2 RF PCB RF receiver 3 Sensor upper section TEMP RH SENSOR 11 20 4 Filter set ISO Coarse ISO Coarse ISO Coarse ISO ePM1 according to ISO 16890 G4 G4 G4 F7 5 Bypass motor BYP...

Страница 17: ...S44 TEMP SENSOR 21 outdoor air n a C1 0 10 V input C2 Bathroom switch C3 n a C4 Malfunction dirty filter alert LED SAI Flash Output voltage at malfunction alert 5 V SA 0 3V E P N L M H 230V 50Hz Swit...

Страница 18: ...18 EN Front view of main PCB 10001047667 0619 zw zw A4 ComfoAir E 350 GEN2 Service Zehnder SI_EN indd 18 11 07 19 13 30...

Страница 19: ...elow view Side view Ma skizzen 10 NL 4 3 Maatschets 40 850 60 235 10 725 490 123 560 160 190 280 5 265 250 100 180 200 CA300 CA400 10 NL 4 3 Maatschets 40 850 60 280 10 725 490 123 560 160 190 280 5 2...

Страница 20: ...e electronics can be damaged by static charging so always take measures to prevent electrostatic discharge e g antistatic belt when handling the electronics Zehnder recommends hiring a specialist clea...

Страница 21: ...it to the service mode Disconnect the power to the unit Remove the 3 screws from the front cover Remove the front cover Remove the heat exchanger Pull on the strap of the heat exchanger Do not cut the...

Страница 22: ...back Press temperature sensor T21 up out of the insulation cover next to the bypass flap While holding the clamp away from the flap pull the flap towards you During installation Place the Zehnder log...

Страница 23: ...eed as follows 1 1 2 2 3 Remove the bypass flap according to the instructions in the corresponding section Set the unit to the service mode Disconnect the power to the unit Remove the 3 screws from th...

Страница 24: ...the front cover Remove the front cover Remove the 3 screws from the display cover Then remove this cover Remove the 4 screws from the electronics cover Then remove this cover 4 5 6 Pull the black con...

Страница 25: ...Contamination dirt and grease Air leakages loose connections Resistance bends dents and blocked valves Valves Resolve any problems detected 4 9 Procedure for completing maintenance 1 2 3 Example repor...

Страница 26: ...ribes how to solve all error codes 5 1 Malfunction alerts on the display of the unit Code Meaning BYPASS MOTOR 11 ERROR Malfunctions in the motor of the bypass valve on the extract air side BYPASS MOT...

Страница 27: ...nit Remove the 3 front cover screws Remove the 3 screws from the display cover Then remove the cover Remove the 4 screws from the electronics cover Then remove the cover Pull the black connector of th...

Страница 28: ...is located on the right 4 5 6 Remove the heat exchanger Pull on the strap of the heat exchanger Do not cut the strap The strap is necessary to pull out the heat exchanger from the unit You can only r...

Страница 29: ...pressure sensor Then pull the sensor sideways from the sensor container 5 6 Resetting errors Most errors will automatically reset themselves once the problem has been resolved The following errors can...

Страница 30: ...rol PCB 2 Go to the next question 2 Are all connectors properly connected to the control PCB See connection diagram in the Section Technical specifications Yes 1 Inspect the fans as described in the m...

Страница 31: ...nd in the malfunction Section Access to the T11 T20 sensor 2 Go to the next question No 1 Connect everything as described in the connection diagram in the section Technical specifications 2 Follow the...

Страница 32: ...22 ERROR Malfunctions in the temperature sensor for the exhaust air outdoor air downstream of the preheater For the right hand unit TEMP SENSOR 12 and 21 are to the centre left of the unit For the le...

Страница 33: ...the control PCB 4 Replace the control PCB as described in the manual supplied 5 Follow the procedure for completing the maintenance No 1 Get the service set for the control PCB 2 Replace the control...

Страница 34: ...escribed in the section Access to the control PCB 2 Go to the next question No 1 Place temperature sensor T21 properly in the insulation cover beside the bypass valve How to get access to this sensor...

Страница 35: ...tem test of the unit as described in the section Carrying out a system test 2 Does the unit have an error Yes Solve the error as described in the relevant malfunction table No Go to the next question...

Страница 36: ...a BYPASS MOTOR 11 ERROR or BYPASS MOTOR 20 ERROR Yes Solve the error as per the relevant resolution table No Go to the next question 3 Has it been cold for an extended period Yes The unit thinks that...

Страница 37: ...bathroom control has finished This takes no more than half an hour No Go to the next question 2 Are the settings of the RF input programmed as per the specifications of the controls See the manual fo...

Страница 38: ...10001047667 0619 zw zw A4 ComfoAir E 350 GEN2 Service Zehnder SI_EN indd 38 11 07 19 13 31...

Страница 39: ...10001047667 0619 zw zw A4 ComfoAir E 350 GEN2 Service Zehnder SI_EN indd 39 11 07 19 13 31...

Страница 40: ...77933 Lahr Germany T 49 78 21 586 392 F 49 78 21 586 406 sales international zehndergroup com www international zehnder systems com ZGNL Manual_10001047667 V0719 EN Subject to change 10001047667 0619...

Отзывы: