6.14  Explanation of the SYSTEM TEST menu

A system test can be initiated in the SYSTEM TEST 
menu.
(MENU>Login>SYSTEM TEST)

Meaning

SYSTEM TEST 
CANCELLED
MAX. BELOW 150 m

3

/h

This error must be resolved in order to
carry out a system test. Otherwise errors 
of the preheater or bypass cannot be 
resolved!

Possible causes:

  HIGH SETTING set lower than 160 m

3

/h

  Air volume of valves not set correctly 

(valves too tight)

  Air ducts have too much resistance

  Outdoor air grille blocked

  ALTITUDE entered incorrectly

  Filters are dirty

  Heat exchanger is frozen

Preset 3 supply air 
(m

3

/h)

ACTUAL (SETTING)

The air volume on the supply side (ODA 
& SUP) is set lower. Accept this or reduce 
the air resistance on the supply side of the 
system. Then carry out another system 
test.

Possible causes:

  Air volume of valves not set correctly 

(valves too tight)

  Air ducts have too much resistance

  Outdoor air grille blocked

  ALTITUDE entered incorrectly

  Filters are dirty

Preset 3 extract air 
(m

3

/h)

ACTUAL (SETTING)

The air volume is lower than set on the 
extract side (ETA & EHA). Accept this or 
reduce the air resistance on the extract 
side of the system. Then carry out another 
system test.

Possible causes:

  Air volume of valves not set correctly 

(valves too tight)

  Air ducts have too much resistance

  ALTITUDE entered incorrectly

  Filters are dirty

  Heat exchanger is frozen

6.15  Explanation of RESTORE TO FACTORY 

SETTINGS menu

The factory settings of the unit are permanently saved 
to the control PCB. Using the RESTORE TO FACTORY 
SETTINGS menu, the unit can be switched back to the 
factory settings. This permanently overwrites all adjusted 
settings. After the reset, the unit will start running as if it 
had just left production. The air specifications, analogue 
input and RF controls (if unit is equipped with) will have 
to be reset/re-programmed. 
If only the malfunction codes need to be reset, then 
use the reset function in menu errors on the first menu 
screen.

6.16  Explanation of control methods

What is SET METHOD?

Regulating involves maintaining the programmed set 
point. If the incoming signal of the desired set point 
deviates, the unit will adapt the outgoing signal to arrive 
at the desired set point.

What is POSITIVE?

In the event of positive regulating, power will go up if 
the measurement is below the set point. In the event of 
a higher measurement, power will go down. Most of the 
pressure sensors use positive regulating. 

Signal

Geschwindigkeit

What is NEGATIVE?

In the event of negative regulating, power is increased 
if the measurement is higher than the set point. In the 
event of a lower measurement, power is decreased. 

Signal

Geschwindigkeit

Speed

Speed

Содержание ComfoAir E 350

Страница 1: ...Cooling Ventilation Filtering Heating ComfoAir E350 Manual for the installer...

Страница 2: ...ew filters Contact details Information given in the Instructions for the user General information about the ventilation system Warranty and liability conditions EC declaration of conformity Replacing...

Страница 3: ...specifications 16 6 4 RF controls 17 6 5 Explanation of VENTILATION SETTINGS menu 18 6 6 Explanation of REPLACE FILTER warning 18 6 7 Explanation of ALTITUDE menu 18 6 8 Explanation of TEMPERATURE men...

Страница 4: ...amage the electronics When working with electronics always take protective measures to prevent electrostatic discharge such as wearing an antistatic wristband If the power cord is damaged it must be r...

Страница 5: ...have received the correct unit type Mounting bracket Documentation Connector set Protective cover Condensation drain adapter 32 mm pipe Condensation drain sealing cap Information available on the iden...

Страница 6: ...n area 90 non condensing IP classification IP 41 ISO classification B Weight 50 kg Filter class ISO Coarse and ISO ePM1 according to ISO 16890 G4 F7 ComfoAir E350 Qv m3 h Pst Pa P W cos SFP Wh m3 Lw s...

Страница 7: ...tective cover of the display C Power cable with 230 V plug not illustrated D 2 adjustment caps E Input for connecting a bathroom switch F 4 connections for the air ducts G 2 condensation drains to dra...

Страница 8: ...door air after preheater VV Preheater S44 TEMP SENSOR 21 outdoor air after preheater n a C1 0 10 V input C2 Bathroom switch C3 n a C4 Malfunction dirty filter alert LED SAI Flash Output voltage at mal...

Страница 9: ...EN 9 Front view of main PCB...

Страница 10: ...180 200 CA300 CA400 Above view Frontal view Below view Side view Ma skizzen 10 NL 4 3 Maatschets 40 850 60 235 10 725 490 123 560 160 190 280 5 265 250 100 180 200 CA300 CA400 10 NL 4 3 Maatschets 40...

Страница 11: ...escribed in the section on the condensation drain 6 Example air duct 7 Example valve 8 Install the air ducts to the unit as described in the section on air ducts Only remove the protective cover just...

Страница 12: ...ir seal siphon To drain the condensation from the unit two bayonet connections are located on the bottom of the unit These connections are not airtight Consequently it is necessary to close the unused...

Страница 13: ...densation on the outside of the duct Zehnder recommends that you fit thermal and moisture resistant insulation to the supply duct from the unit up to the supply valves This will prevent unnecessary te...

Страница 14: ...on C Child lock is engaged D Icon for activating the menu screen E Icon for activating the comfort temperature menu F Icon for activating the filter replacement menu G Icon for activating the error re...

Страница 15: ...HIGH SETTING OUTDOOR AIR TEMPERATURE MEDIUM SETTING EXHAUST AIR TEMPERATURE LOW SETTING EXTRACT AIR TEMPERATURE FANS Readout SUPPLY AIR TEMPERATURE SUPPLY FAN RPM FIREPLACE MODE YES NO PREHEATER TEMPE...

Страница 16: ...ve using a flow meter Write down the air flow for these valves Adjust the opened valves to the required air flow per room Measure the air flow again at each opened valve using a flow meter Check that...

Страница 17: ...n the display of the unit to ON MENU SERVICE MENU RF SETTING ACTIVATION ON You now have 10 minutes to register the RF control Set METHOD on the display of the unit to DISCRETE CONTROL MENU SERVICE MEN...

Страница 18: ...before the filters need to be replaced This gives the user enough time to purchase new filters before the dirty filters are to be replaced It is possible to set the alert to appear earlier by increas...

Страница 19: ...air is conveyed This ensures longer operation in frost conditions until deactivation 6 12 Explanation of ANALOGUE 0 10 V menu standard and RF SETTING optional The unit can be controlled with any anal...

Страница 20: ...es too tight Air ducts have too much resistance ALTITUDE entered incorrectly Filters are dirty Heat exchanger is frozen 6 15 Explanation of RESTORE TO FACTORY SETTINGS menu The factory settings of the...

Страница 21: ...ALUE for PI Controller Proportional means that the difference between the desired and measured value is increased by the value k Integral means that the error is constantly summed and that the unit co...