 25

System functions

3.10.3 Malfunctions (or problems) without alerts

An overview of the malfunctions (or problems) without notifi cations is given below.

Problem/Malfunc-
tion

Indication

Check / action

System switched off

Power supply on

Check

 the fuse on the 

PCB panel.

•  If the fuse is OK, the control PCB is 

defective.

No power supply

Mains power

 is off.

High intake temper-
ature in summer

Bypass remains closed

Reduce

 the comfort temperature.

Low intake tempera-
ture in winter

Bypass stays open

Increase

 the comfort temperature.

Little or no air sup-
ply; shower remains 
damp

Filters blocked

Replace

 the fi lters.

Valves blocked

Clean

 the valves.

Exchanger clogged by dirt.

Clean

 the exchanger.

Exchanger frozen

Defrost

 the exchanger.

Fan dirty

Clean

 the fan.

Ventilation ducts blocked

Clean

 the ventilation ducts.

Too noisy

Fan bearings defective

Replace

 the fan bearings.

Fan settings

Change

 the fan settings.

Slurping noise

•  Siphon is empty
•  Siphon does not seal properly

Reconnect

 the siphon.

Whistling noise

•  An air gap somewhere

Seal

 the air gap.

Airfl ow noise

• Valves do not close onto duct.
• Valves not open far enough

Reinstall

 the valves.

Reset

 the valves.

Condensation leak

Condensation drain clogged

Unblock

 the condensation drain.

Condensation from exhaust duct 
does not run into leakage tray

Check

 whether the connections 

are correct.

Corded 3-position 
switch not working

Cabling is Not good

Check

 the wire-circuit of the 

3-position switch by 
measuring the voltage:

•  Voltage only on N & L3:SFlb[Fans ro-

tate in position 1].

•  Voltage only on N & L3 & L2:SFlb[Fans 

rotate in position 2].

•  Voltage only on N & L3 & L1 or 

N & L3 & L2 & L1:SFlb[Fans rotate in 
position 3].

Switch is defective

Wireless 3-position 
switch not working

Battery is discharged

Check

 the battery.

•  

Replace

 the battery (if necessary).

Содержание ComfoAir 350

Страница 1: ...ComfoAir 350 Manual...

Страница 2: ...II All rights reserved This manual has been compiled with the utmost care The publisher cannot be held liable for any damage caused as a result of missing or incorrect information in this manual...

Страница 3: ...3 2 1 3 Bypass for free cooling 3 2 1 4 Frost protection 3 2 1 5 Chimney sweep programme 3 2 2 Available operating devices 4 2 2 1 Display 4 2 2 2 3 position switch 4 2 2 3 Bathroom switch 4 2 3 Main...

Страница 4: ...sioning the ComfoAir 16 3 7 1 Display on the unit 16 3 8 Programming air specifications 20 3 9 Maintenance by the installer 20 3 9 1 Inspecting the heat exchanger and fans 21 3 10 Malfunctions 22 3 10...

Страница 5: ...r is covered by a manufacturer s war ranty for a period of 24 months after fitting up to a maximum of 30 months after the date of manu facture Warranty claims may only be submitted for material faults...

Страница 6: ...gulations warnings com ments and instructions as prescribed in this manual at all times Keep this manual with the ComfoAir throughout its life Instructions with regard to cleaning or replacing the fil...

Страница 7: ...E 2 1 2 Heat recovery Besides ensuring a healthy balance between in coming and outgoing air the ComfoAir also pro vides the benefits of heat recovery Heat recovery means that heat from the extracted...

Страница 8: ...witches can be fitted in the house e g in the kitchen The following types of switches can be used Type 1 J Standard 3 position switch Type 2 J 3 position switch with LED for malfunction and filter ale...

Страница 9: ...ures that the ComfoAir does not switch back to the default or preprogrammed setting when de activated but first waits for the overrun timer to run its course Once the programmed overrun timer is compl...

Страница 10: ...the HIGH SETTING 0 Min 15 Min 0 Min P22 Optional Note Only applies to systems fit ted with a corded switch and a second switch in the bathroom Low voltage input Overrun timer for the bathroom switch t...

Страница 11: ...to systems fit ted with an RF switch Overrun timer for ventilation setting 3 After pressing for LONGER 2 sec the ComfoAir runs at the HIGH setting for x minutes and then automatically returns to the...

Страница 12: ...nstruction phase the ventilation system could have be come dirty with building dust Replace the filters at least once a year 2 3 2 Cleaning the valves in your dwelling The ventilation system may be fi...

Страница 13: ...filter dirty alert both indicators will flash red 3 times After that both indicators will light up green once more The malfunction indicator on the 3 position switch will not light up in the event of...

Страница 14: ...xchanger F PCB panel H with connections for the fans the bypass temperature sensors T1 to T4 the 3 position switch with or without malfunction and filter indication optional and the bathroom switch op...

Страница 15: ...A HIGH SETTING 260 m3 h at 140 Pa 0 81 A MAXIMUM 350 m3 h at 240 Pa 1 77 A Electricity Power supply 230 50 V Hz Cos phi 0 50 0 60 Supply fan noise level at 0 m Position Ventilation capacity Value ABSE...

Страница 16: ...A Electricity Power supply 230 50 V Hz Cos phi 0 50 0 60 Supply fan noise level at 0 m Position Ventilation capacity Value ABSENT SETTING 40 m3 h at 4 Pa 36 db A LOW SETTING 140 m3 h at 40 Pa 54 db A...

Страница 17: ...ctions 3 3 Dimension sketch 801 35 214 761 180 851 845 702 160 151 354 348 264 161 572 625 269 172 172 CONDENSATION DRAIN LEFT HAND VERSION CONDENSATION DRAIN RIGHT HAND VERSION CABLE CONDENSATION DRA...

Страница 18: ...the exhaust connections of the ComfoAir with si lencers located directly against the unit For fur ther information please contact Zehnder A 10mm gap should be left under the in side doors in order to...

Страница 19: ...ir Exhaust air Supply air Return air Return air Supply air Exhaust air Outside air 3 6 2 Connection of the condensation drain ComfoAir 350 LEFT ComfoAir 350 RIGHT Warm exhaust air is cooled by the out...

Страница 20: ...staller The ComfoAir s bypass valve will not work for the first 4 minutes after a power cut un less the programme mode is activated 3 7 1 Display on the unit select menu up OK down supply off supply o...

Страница 21: ...the capacity in of the sup ply fan in HIGH POSITION 18 100 nL HL 70 90 P38 Current capacity in of the exhaust fan Current P39 Current capacity in of the supply fan Current Menu P4 Reading the tempera...

Страница 22: ...r fitted 1 Enthalpy exchanger with RH sensor 2 Enthalpy exchanger without RH sensor 0 No 2 Yes 0 Note If an enthalpy exchanger without a sensor is selected then the enthalpy pro gramme will not be act...

Страница 23: ...ting the self test the ComfoAir will run at maximum RPM Immedi ately after activating the self test the bypass valve opens and closes P77 Resetting filter dirty counter 0 1 0 Note This resets the coun...

Страница 24: ...whether both fans function in the three speed settings Switch the ComfoAir to high speed Install all valves and set the valves according to the settings Change the fan settings in P menus P30 to P37 o...

Страница 25: ...e tray F E F G Left hand E F G Right hand Remove the heat exchanger from the leakage tray F The heat exchanger may contain some re sidual water Clean the heat exchanger if so required Submerge the hea...

Страница 26: ...s a malfunction alert will appear on the screen of the digital operating device However malfunction alerts may not appear on the digital operating device in all cases even though there is a malfunctio...

Страница 27: ...fan malfunction Remove filters front and metal cover Does the fan connection on the PCB register 230 VAC Yes Activate self test P76 op 1 Is fan control voltage detectable on PCB 1 5 10 VDC Yes Discon...

Страница 28: ...13 071 13 237 20 12 339 12 491 12 644 21 11 801 11 941 12 082 22 11 291 11 420 11 550 25 9 900 10 000 10 100 30 7 959 8 057 8 155 Temperature C A5 Malfunction of bypass motor Remove filters front and...

Страница 29: ...entilation ducts Too noisy Fan bearings defective Replace the fan bearings Fan settings Change the fan settings Slurping noise Siphon is empty Siphon does not seal properly Reconnect the siphon Whistl...

Страница 30: ...rt Article number 1 Fans left and right 400200010 2 ComfoAir PCB 400300010 3 Temperature sensor T2 T4 in scroll casing of both fans 400300022 4 Temperature sensor T1 T3 in top of unit near the electro...

Страница 31: ...own Brown Blue Blue Brown Black Grey Forst free Supply Exhaust White Yellow Blue Brown White Brown White Red Black Blue Yellow White Brown White Brown White Black Red Bypass valve Forst free element v...

Страница 32: ...own Brown Blue Blue Brown Black Grey Forst free Exhaust Supply White Yellow Blue Brown White Brown White Red Black Blue Yellow White Brown White Brown White Black Red Bypass valve Forst free element v...

Страница 33: ...l number where available Location of fan units 1 2 3 4 5 1 3 Installation Engineer s Details Engineer s Name Company Address Line 1 Address Line 2 Telephone Number Post Code 1 4 Commissioning Engineer...

Страница 34: ...relevant system installation clauses been followed as details in Tables 1 3 5 and 7 as applicable Yes No If any deviation from Tables 1 3 5 and 7 these should be detailed here Description of installe...

Страница 35: ...Has all protection packaging been removed including background ventila tors such that system is fully functional Yes No For ducted systems has the ductwork installation been installed in such manner t...

Страница 36: ...s Refer to Table 5 1a in ADF Extract Fan 1 Extract Fan 2 Extract Fan 3 Extract Fan 4 Extract Fan 5 For kitchen extract canopies only the highest setting needs to be recorded 3 3 Air Flow Measurements...

Страница 37: ...w High Rate l s Refer to Table 5 1b ADF Measured Air Flow Low Rate l s Design Air Flow Low Rate l s Refer to Table 5 1b in ADF Living Room 1 Living Room 2 Dining Room Bedroom 1 Bedroom 2 Bedroom 3 Bed...

Страница 38: ...Company register Zwolle 05022293 EG declaration of conformity Machine description Heat recovery units ComfoAir 350 series Complies with the following directives Machinery Directive 98 37 EG Low Volta...

Страница 39: ......

Страница 40: ...Zehnder Comfosystems Unit 1 Brookside Avenue Rustington West Sussex BN16 3LF J E Stork Ventilatoren B V 849050683 0509...

Отзывы: