15 - EN
When reassembling the leakage tray the
openings in the leakage tray must be on the
side of the condensation drain.
11. Inspect and if necessary clean the heat exchang-
er.
- Use a soft brush to clean the fins.
- Use a vacuum cleaner or air gun (no high
pressure) to remove dirt and dust.
Always clean against the direction of
the airflow. This prevent dirt from get-
ting stuck in the heat exchanger.
Standard heat exchanger only:
a. Submerge the heat exchanger several times in
hot water (max. 40 °C).
b. Rinse the heat exchanger with clean hot tap wa-
ter (max. 40 °C).
c. Clasp the heat exchanger between both hands
(on the coloured side surfaces) and shake the wa-
ter from the heat exchanger.
Do not use aggressive cleaning agents or
solvents.
If the fans also need maintenance do not re-
install the heat exchanger yet.
12. If no more maintenance is necessary install all
parts in reverse order, reconnect the power and
carry out the self-test in accordance with menu
P76.
Fasten the screws to a maximum of 1.5 Nm.
This is roughly equal to speed 2 of an aver-
age battery-powered drill.
2.9.2 Inspecting and cleaning the fans
Check the fans once every 2 years.
1. Remove the heat exchanger as instructed in the
maintenance chapter of the heat exchanger.
2. Remove the small plastic panel (H) in front of the
control circuit board panel by unscrewing the
two screws.
3. Release the connectors (K) and the earth wire on
the control circuit board panel and fully remove the
cables including the two grommets (K).
4. Remove the entire scroll casing (L) by pressing
the click fasteners.
5. Remove the inflow nozzle by pressing the click
fasteners surrounding the scroll casing.
6. Inspect and if necessary clean the fans.
- Use a soft brush to clean the fan impellers.
- Use a vacuum cleaner to remove dust.
L
K
H
Do not damage the fan impellers or tempera-
ture sensor.
7. If no more maintenance is necessary install all
parts in reverse order, reconnect the power and
carry out the self-test in accordance with menu
P76.
Fasten the screws to a maximum of 1.5 Nm.
This is roughly equal to speed 2 of an aver-
age battery-powered drill.
Содержание ComfoAir 350 Basic Series
Страница 1: ...Cooling Fresh Air Clean Air Heating ComfoAir 350 Basic Installer manual...
Страница 4: ...EN IV...
Страница 30: ...EN 26...
Страница 31: ...27 EN...