7 - EN
2.4 Installation conditions
In order to determine whether the ComfoAir can be
installed in a certain area, the following aspects must
be taken into account:
■
The ComfoAir must be installed according to the
general and locally applicable safety and installa-
tion regulations of power and water companies, as
well as the instructions in this manual.
■
The system must be fitted to allow sufficient room
around the ComfoAir for the air connections and
supply and exhaust ducts as well as for carrying
out maintenance activities.
■
The ComfoAir must be installed in a frost-free space.
The condensation must be drained off frost-free, at a
gradient and incorporate a 'U' bend.
We do not recommend installing the Com-
foAir in areas with a higher average humidity
(such as bathroom or toilet). This will prevent
condensation on the outside of the ComfoAir.
■
The room must offer the following provisions:
- Air duct connections.
- 230V electrical connection.
- Provisions for the condensation drain.
- Wiring for a wired 3-position switch
(optional).
■
A gap should be left near the doors in order to
ensure effective and draughtfree airflow in the
house. A gap under the inside doors must be at
least 10mm.
If these openings are obstructed, due to
draught excluders or deep-pile carpet, the
airflow in the house will stagnate. As a result,
system performance will be compromised or
fail altogether.
2.5 Installation of the ComfoAir
2.5.1 Transport and unpacking
Take the necessary precautions when transporting
and unpacking the ComfoAir.
Make sure the packing material is disposed
of in an environmentally friendly manner.
2.5.2 Checking the delivery
Contact your supplier immediately in case of dam-
age or an incomplete delivery. The delivery should
include:
■
ComfoAir;
Check the identification plate to ensure that it is
the required type.
■
4 x 45
O
connection bends;
■
Mounting bracket;
■
Documentation.
The ComfoAir is supplied in the following types:
Type
ComfoAir 350 L Basic
ComfoAir 350 R Basic
Meaning of the suffixes:
* L
=
Left version
* R
=
Right version
2.6 Mounting of the ComfoAir
2.6.1 Mounting on the wall
Mount the ComfoAir against a wall with a minimum
mass of 200 kg/m
2
. For other types of wall, we recom-
mend using the Zehnder mounting frame on the floor
(available as an optional extra). This reduces contact
noise as much as possible. The ComfoAir does not
require any space at the sides for effective operation.
Do not mount the side of the ComfoAir
against the wall due to the risk of impact
sound.
1. Fasten the mounting bracket to the wall. Make
sure it is level and at least 878mm from the floor
(depending on the type of condensation drain se-
lected).
Leave a minimum space of 1m in front of the
ComfoAir for carrying out maintenance.
2. Hang the ComfoAir on the mounting bracket.
3. Mount the condensation drain under the Com-
foAir. The stated dimension of 235 mm is an in-
dication only, and is dependent on the type of
condensation drain selected.