17
3.1.7 Once the unit is commissioned check that the system is operating correctly by turning the hardwired switch to
the differing settings, i.e. the ZGS2 switch or ZGRC1 Controller will activate the unit between low and high
speed settings, alternatively the ZGS1 will activate the unit between low, AUX and high speed settings.
• Performance levels can be verified at both extract and supply air valves using an appropriate method
such as a rotating vane anemometer and air cone kit.
• Refer to performance graph for ComfoAir 155 WM airflow characteristics
(See Section 3.1.8).
Note: All settings are stored within the ComfoAir 155 WM unit’s memory and should NOT be lost in the
event of a power failure. When power is restored, the unit should revert to normal running with all
settings unchanged. Likewise, reminder indicators are NOT reset.
3.1.8
Performance Graph
- Airflow Characteristics
S E T U P
M E N U
>
<
p a s s w o r d
e n t r y
P A S S W O R D
X X X X
3.1.9
To Re-activate Commissioning Set-up Wizard
In the event that the unit needs to be adjusted once the commissioning wizard has been completed;
•
Press the control button to activate the unit.
•
Rotate button until the screen displays "Setup Menu".
•
Press button to select.
•
Enter Password "1010" by rotating the button to the respective
number and press to select (this has to be completed for each
number prior to continuing).
•
Once commissioning setup has been re-activated, rotate button to
desired setup change and follow
(see Recommissioning Menu
Structure 3.1.10),
press the button to select.
•
Current set-up will be shown, change to new requirement & press
button to confirm.
•
Rotate button 'right' to move to next section or 'left' to return to
previous set-up.
•
Complete all sections requiring changes.
•
Upon completion, to save and exit, rotate button to "Exit", press
button to confirm.