2.3. Storage
The material should be stored in a sheltered, dry place as the packaging is not suitable for storage in bad weather.
2.4. Supply limit
The Zehnder EDT2 Wall-Mounted Touchscreen User Controller is delivered alone.
Depending on the type of support (wall, partition, breeze block, brick, etc.), it is necessary to provide suitable fixings
(dowels) and screws of the appropriate length and diameter (diameter < 4 mm with recommended Phillips head).
3. Functions
The Zehnder EDT2 Wall-Mounted Touchscreen User Controller is a touch-sensitive room control. It provides the
interface between the machine and the end user (occupant) through the following features:
Settings
Temperature setpoint offset in the
range of -3 °C to +3 °C (in 0.5 °C
increments)
Range changeable from the CLD-283 controller within a limit of -5 °C to +5 °C.
Activation of a 120-minute restart
Press and hold
Time can be changed from the CLD-283 controller up to 240 minutes (in
1-minute increments). When the restart is activated, it can be stopped at any
time by simply turning off the function manually. It must be reactivated when the
programmed time has elapsed.
Putting the display on standby
Press and release
Information (display)
Current ventilation mode*
Ventilation running in reduced mode
Ventilation running in normal mode
Current ventilation status*
Fixed display (= no ventilation) / flashing display (= active ventilation)
Current operating mode*
Operation on a timed schedule or external overruling activated
Current status of external
overruling
At least one external overruling activated (restart, external DI controls reduced /
normal operation, GTC HR796)
Current temperature setpoint
Supply temperature setpoint if supply temperature is controlled
Return temperature setpoint if return temperature is controlled
Current measured temperature
Supply temperature if supply temperature is controlled
Return temperature if return temperature is controlled
Presence of alarms
The presence of an alarm is indicated by a small flashing light bulb. AXXX is
displayed instead of the temperature when an alarm that causes the machine to
stop is active (XXX represents the ID number of the alarm - e.g. A168 for alarm
no. 168).