Troubleshooting
(continued)
7
If the current flowing into the
Zebrastat
through these two wires should exceed 3
Amps, the breaker will ‘trip’, and the
lower
Trip
LED will light. The breaker will stay in this
‘tripped’ condition until the power is removed
from one of the leads for about 15 seconds.
(Some electronic thermostats may start a set/
reset cycle as they lose power and drop out.)
A typical problem causing a fuse to blow on
one of these boards is a shorted thermostat
wire. Diagnosing which wire is accomplished
much easier with a
ZebraStat
: Hook up the
ZebraStat
as described above. When the
Zebrastat
’s breaker trips, remove power to
the system for 15 seconds. While the
power
is off remove one thermostat wire at a time
from the control
b
oard, turning on the power
again after each
disconnection. When th
e
Trip
LED does NOT
light up after removing a wire,
the suspect circuit has been found. If all ex
-
ternal low voltage control wires are removed,
and the
Trip
LED still lights, it’s time to suspect
that the
board itself may have a problem.