Page - 62/79
AF6ZP0AL - COMBIAC0 & ACE0 - User Manual
B) If the alarm occurs during motor running, check:
- Motor
connections
-
If motor phases windings/cables have leakages towards truck frame
-
That the LC power contact closer properly, with a good contact
-
If no problem are found on the motors, the problem is inside the
controller.
3) “VMN
HIGH”
Cause 1:
Before switching the LC on, the software checks the power bridge: it turns on
alternatingly the Low side Power Mosfets and expects the phases voltage to
decrease down to -BATT. If the phases voltage do not decrease, this alarm
occurs.
Cause 2:
This alarm may occur also when the start up diagnosis is overcome, and so
the LC is closed. In this condition, the phases’ voltages are expected to be
lower than 1/2 Vbatt. If it is higher than that value, fault status is entered.
Troubleshooting:
A) If the problem occurs at start up (the LC does not close at all), check:
-
Motor internal connections (ohmic continuity)
-
Motor power cables connections
-
If the motor connection are OK, the problem is inside the controller
B) If the problem occurs after closing the LC (the LC closed and then opens
back again), check:
- Motor
connections
-
If motor phases windings/cables have leakages towards truck frame
-
If no problem are found on the motors, the problem is inside the
controller
4) “POWER MOS SHORTED”
Cause: Before switching the LC on, the software checks the power bridge: it
turns on alternatingly the Low side and High side Power Mosfets and expects
the phases voltage to decrease down to –BATT (increase up to +Batt). If the
phases voltage do not follow the comands, this alarm occurs.
Troubleshooting:
This type of fault is not related to external components; replace the controller.
5) “COIL SHORTED”
Cause:
This alarm occurs when there is a short circuit of one of the coils connected
to outputs of the Combiac0 (LC coil or EB coil). After the overload condition
has been removed, the alarm exits automatically by releasing and then
enabling a travel demand.
Troubleshooting:
A) The typical root cause for this error code to be displayed is in the harness
or in the load coil. So the very first check to carry out concerns
connections between controller outputs and loads.
B) In case no failures/problems have been found externally, the problem is
in the controller, which has to be replaced.
6) “DRIVER
SHORTED”
Cause:
The driver of the main contactor coil is shorted or the coil is disconnected.
Troubleshooting:
A) Check if there is a short or a low impedance pull-down between NMCC
Содержание COMBI AC0
Страница 27: ...AF6ZP0AL COMBIAC0 ACE0 User Manual Page 27 79 8 DRAWINGS 8 1 Mechanical drawing ...
Страница 28: ...Page 28 79 AF6ZP0AL COMBIAC0 ACE0 User Manual 8 2 Connection drawing ACE0 ...
Страница 29: ...AF6ZP0AL COMBIAC0 ACE0 User Manual Page 29 79 8 3 Connection drawing CombiAC0 ...
Страница 33: ...AF6ZP0AL COMBIAC0 ACE0 User Manual Page 33 79 10 3Description of the console menu 10 3 1 ACE0 COMBIAC0 Menu ...