Safety Relay MINOS SD1E
EN
LED off:
LED on:
Explanation / Measure
U
B
I1
I2
K
1/2
Overvoltage at A1/A2:
•
Measure the supply voltage and adjust if necessary.
Note!
The maximum permissible supply voltage is DC 26.4 V
The safe relay contact 13-14 is not enabled:
•
Auto-start: Check if the reset circuit is connected to terminal S21
with U
B
. Check the synchronisation time between I1 and I2. If I1 is
present before I2, then the maximum time between the two signals
should not exceed 300 ms
•
Monitored manual start: Check the wiring of the reset circuit. Does
the reset button work properly?
Note: The falling edge of the start signal is evaluated (contact
opens)
•
Check if the feedback circuit through some connected contactors
or expansion modules work properly. If not, replace the faulty
device and perform a reset
•
Check the correct position of the Config-Switch S2 (see chapter 7
“Function”)