Current transformer ratio for Module-1
can be adjusted from 0 to 100.)
e g
:
F o r 1 0 0 : 5 A t y p e c u r r e n t
transformer the Ctr 1 parameter would
be 100/5 or 20
Current Transformer
Calculating set value for heater failure
Set Value = [(Current value without f
Current value with heater failure )] / 2
eg. A 200V system with three1KW heaters
would normally draw 15 amps
[1000 / 200 ]*3 = 5A *3 = 15A
If one of the heaters is out of order, the current
draw is now 5A*2 or 10A. The Set Value must
be adjusted to (15+10) /2 or12.5A
HEATER BREAK ALARM
to Module 1
PNEUMONIC REPRESENTATION
1-877-798-7287
P.7
MOTORIZED VALVE CONTROL
SET
°C
AUTO
°C
AUTO
°C
AUTO
AUTO
SET
SET
SET
°C
ESM 7750 v10R7
°C
AUTO
°C
AUTO
SET
°C
AUTO
SET
°C
AUTO
SET
°C
SET
°C
AUTO
SET
°C
SET
°C
SET
process
set
value
alarm 1
set
value
alarm 2
set
value
alarm 3
set
value
tune
auto
tune
Operation
type
ramp/soak
control
motorized
valve
control
bumpless
transfer
alarm
latch
cancelling
top
display
bottom
display
soft
start
ramp/
soak
tolerance
ramp/
soak
steps
PU=RS nbr.
tr=ramp time
tS=soak time
up to 8 R/S
steps
Ramp/Soak
menu
EMO-700 relay output
module must be plugged
into Module-1 socket.
100 ... 240 V
Opening
Relay
N
L
Supply
Switch
Closing
Common
Opening
Valve
Supply
Input
~
M
~
~
V
n n
Ope i g Closing
MOTORIZED VALVE
50/60 Hz
1A T
Fuse
~
Max. 3A T
Fuse
~
10
Input/Output
Module-2
MODULE-2
Output-3
Closing
Relay
1
11
2
13
3
14
4
17
5
18
6
NO
C
3A@250V
NO
C
5A@250V
EMO-700
MODULE-1
~
~
Communication
Module
(RS-232(standard)/
RS-485(optional))
7
NC
Control Output
200V
1kW*3
Heater
~
10
11
CT
MODULE-1
In the RUN LIST grouping of the
OPERATOR’s section, select HEAT or
COOL for parameter ULSL.
The parameter can be adjusted
from 5 to 600 seconds. It defines the time
required to open the valve completely.To
determe this parameter correctly, close the
valve manually. Be sure the valve is fully
closed; then reopen it manually without
stopping and measure how long it took to
reopen it completely. Add 5% to this value
and enter it for this parameter.
The parameter determines the
increments as a percentage of the Ultt
parameter and can be adjusted from 0.1 to
5.0 %. If the valve oscillates while opening
or closing, INCREASE this parameter’s
value!
Graphic representation of Ramp and Soak function
Process
Set value
PU-3
Time
Start
tr_1
tS_1
tr_4 tS_4
PU-1
PU-2
PU-4
PU-5
PU-6
PU-7
PU-8
tr_2
tS_2
tr_3 tS_3
4 ramp soak ( = )
4 ramp soak ( = )
8 ramp soak ( = )
Содержание ESM 7750
Страница 2: ...17 18 output 3...