Front Panel Description

Entering Process Set Value and Parameters

Setting the process values:

When the 

 button is pressed, the SV LED, next to the process value on the bottom 

!

display, flashes. Adjust the desired process set value using the 

 and 

buttons. 

!

!

Press the 

 button again to save the new value to memory. If, instead, the 

 

 

!

!

button is pressed, the new set value isn’t saved to memory and the unit exits the 
setting mode. 

You can't change the SV value when the AT LED is lit.

Setting the alarm values:

All outputs on the device can be configured as alarms. Alarm set values are shown 
as 

ALr1

ALr2

 and 

ALr3 

in the 

SET LIST

 menu. To access the 

Set Lıst

 menu press the  

  button then the 

 button. Pressing the 

 button agaın allows you to 

!

!

!

access and change the values of 

PSEt

ALr1

ALr2

 and 

ALr3

.

Observing and changing parameter values:

The  parameters  have  been  divided  into  three  groups:  Operator,  Technician  and 
Calibration. The calibration parameters can be accessed by the manufacturer only. 
The operator can not access the parameters for running mode and configuration. 
Whenever you want to enter either the operator’s or technician’s parameter groups, 
the  device  will  require  a  password.  The  default  value  of  the  user-changeable 
passwords ıs “0”. To enter new passwords, you must first access the technician’s 

parameters and scroll to “PASS ConF”. After entering the password press the 

 

!

button to save it to memory. 

You can access the main titles of the menu by using the 

 and

 

 buttons. Press 

!

!

the 

   button to move to the next level of any menu. Change the value of your 

!

chosen  parameter    by  using   

  and   

    buttons.  The  new  value  is  saved  to 

!

!

memory by using the 

 

  Button.

!

°C

OP1

SV

°F

OP2

OP3

AT

AUTO

MAN

RAMP

REM

Output1(Process or Alarm) LED

An LED indicator for units other than °C and °F 

Output2(Process or Alarm) LED

Output3(Process or Alarm) LED

Automatic operation LED (for process output)

Manual operation LED (for process output)

LED for Ramp&Soak operations 

LED for operation with remote set value

Process set value LED

Autotune LED

Display & Indicators

°F unit LED

°C unit LED

Parameters

Table-1 (Process Input Type and Scale selection)

0

1

2

4

6

8

10

12

14

16

18

3

5

7

9

11

13

15

17

19

L(FeConst DIN43710)
L(FeConst DIN43710)
J(FeConst IEC-584)

K(NiCrNi DIN/IEC)

R(Pt13%RhPt DIN/IEC)

S(Pt10%RhPt DIN/IEC)

T(CuConst DIN/IEC)

B(Pt18%RhPt DIN/IEC)

E(CrConst DIN/IEC)

N(NicrosilNisil DIN/IEC)

C(... DIN/IEC)

R(Pt13%RhPt DIN/IEC)

S(Pt10%RhPt DIN/IEC)

T(CuConst DIN/IEC)

B(Pt18%RhPt DIN/IEC)

E(CrConst DIN/IEC)

N(NicrosilNisil DIN/IEC)

C(... DIN/IEC)

J(FeConst IEC-584)

K(NiCrNi DIN/IEC)

-100°C

-100.0°C

-200°C

-200°C

0°C

0°C

-200°C

-200°C

-150°C

-200°C

0°C

-199.9°C

-199.9°C

0.0°C

0.0°C

-199.9°C

-199.9°C

-150.0°C

-199.9°C

0.0°C

-148°F

-148.0°F

-328°F

-328°F

32°F

32°F

-328°F

-328°F

-238°F

-328°F

32°F

-199.9°F

-199.9°F

32.0°F

32.0°F

-199.9°F

-199.9°F

-199.9°F

-199.9°F

32.0°F

850°C

850.0°C

900°C

1300°C

1700°C

1700°C

400°C

400°C

700°C

1300°C

2300°C

900.0°C

999.9°C

999.9°C

999.9°C

400.0°C

400.0°C

700.0°C

999.9°C

999.9°C

1562°F

999.9°F

1652°F

2372°F

3092°F

3092°F

752°F

752°F

1292°F

2372°F

4172°F

999.9°F

999.9°F

999.9°F

999.9°F

752.0°F

752.0°F

999.9°F

999.9°F

999.9°F

Process Input Type(TC)

Scale(°C)

Scale(°F)

0

1

PT 100
PT 100

-200°C

-199.9°C

-328°F

-199.9°F

650°C

650.0°C

1202°F

999.9°F

Process Input Type(RTD)

Scale(°C)

Scale(°F)

0

1

2
3
4

0...50 mV
0...5 V
0...10 V
0...20 mA
4...20 mA

Configurable

Process Input Type(DC Voltage and Current) Scale

Configurable
Configurable
Configurable

Configurable

SET

Keyboard

Access all menus and to move 
up to another menu.
Access process set value and OK 
button when in the program mode.

Increase the parameter values 
and access the program menus.
Decrease the parameter values 
and access the program menus.

There are three options: you can have two independent 4 segment processes (essentially 
giving you two recipes) or one 8 segment process. 
If you want only one Ramp, use the Stra parameter. You do not have to use the Pu, Tr and 
TS parameters. 
By using the Stra you are defining the amount of time the controller will take to get the 
temperature to the Set Value (time becomes the overriding factor)

.

If you want more than one R & S, make sure that Stra = 0

.

Then choose rsty according to the number of segments desired.
If you want the controller to shut down after it has gone through all the R & S segments, it 
must be running in the Manual Mode (Operator Parameters – Run List).
If this parameter is defined as AUTO, then, at the end of the final segment, the controller 
will work to keep the temperature at the final target value.
To run the R & S, Rssl in the Operator’s Parameters must be set to RUN via the front 
mounted touch pad
OR
via an input module, EMI-

7

00, which can be plugged into the

 

controller. This is further 

explained on page 

4

.

Notes on Ramp and Soak

ESM 7750 Programming Guide

Abbreviations

Parameters are listed in the left hand column in 

bold lettering 

followed by its 

description and available choices. Some abbreviations are defined as follow:

 AT

 Full Scale (or Max. Scale)

 Autotune

 HYS

 FS

 Process Value

 Hysteresis

 PV

P.3

 1-877-798-7287

Minimum Operating Value
Maximum Operating Value

Self Tune

Process Set Value or PSET

SV

Su-u

Su-L

ST

PSET

ALr1

ALr2

ALr3

This is the device’s process set value. If there isn’t any extra module in the device, 
this parameter is used for Output-3.

Process and Alarm Set Value Parameters

 (SET LIST)

OPERATOR PARAMETERS

Module-1’s alarm set value when installed & configured as an alarm output.

Tuning and Operating methods (RUN LIST) see p5 for explanation of tuning methods

tUnn

This parameter defines the tuning type. 

NO

 

=

Tuning is inactive.

ATUN=

Only Autotune is active.

STUN=

Only Selftune is active.

AT.ST=

Autotune and selftune are active.

attn

NO

=

 Autotune

 is inactive.

YES

=

 Autotune

 is active.

rSSL

Ramp-Soak Function.

oFF

=ramp-soak inactive

run

=Ramp-Soak is active 

hold

=ramp-soak is paused

bpLt

Bumpless Transfer

NO

=bumpless transfer is inactive.

YES=

Bumpless Transfer is active.

Display Parameters (DISP LIST)

Module-2’s alarm set value when installed & configured as an alarm output.

Output-3’s alarm set value when configured as an alarm output.

AUtO

AUTO

= Auto process mode.

MAN

=Manual process mode.

Ramp / Soak Parameters (rmP SoA)

StrA

From 0 to 99h 59min. (Inactive if 0.0)

rStO

From 0 to 50% of SV. (Inactive if 0). If rSto or ramp & soak functions have 
been selected, then (set value-rSto)<starting temp<(set value+rSto). The 
unit operates within this range for the duration selected.

rSty

Ramp-Soak type

0

=1-4 segment

1

= 5-8 segment

2

=1-8 segment

PU-1to 8

Target SV (

SU-L

 to 

SU-U

)

Tr-1 to 8

Ramp segment time (from 0 to 99h 59min.)

TS-1 to 8

Soak segment time (from 0 to 99h 59min)

ULSL

If output module 1 is a relay output, then this parameter can be used to define the 
motorized valve control form. Output 1 to open and Output 3 to close the valve:
No=inactive HEAt=operates with heating PID

CooL=operates with cooling PID

LtCC

High Limit Latch Cancelling. If an Alarm output was configured as a latched 
output and that output is not in the latched condition, it can be returned to a 
non latching alarm output by entering YES. Once cancelled LtCC=NO

SET

°C

AUTO

°C

AUTO

SET

°C

AUTO

see operator 

parameters

see technıcıan 

parameters

factory settıngs

Programming Mode - Main Menus

ESM 7750 v10R7

Process &
Parameter
Display

Process Set Value, 
Alarm Set Value &
Parameter display

tdSP

Defines the function of the top display.

0

=PV , 

1

= SV-PV, 

2=

2nd analog input’s measured value (if unit is fitted with this option)

bdSP

Defines the function of the bottom display.

Note: If device is running in manual mode, the bottom display shows % Power

.

0=

SV

1=

%power

2=

ramp-soak dısplay

 3 = 2nd sensor’s measured value

4 = CT input measured value

Содержание ESM 7750

Страница 1: ...be taken to avoid injury from metal burrs which might be present The equipment can loosen from vibration and become dislodged if installation parts aren t properly tightened WARNING Before beginning...

Страница 2: ...17 18 output 3...

Страница 3: ...e two independent 4 segment processes essentially giving you two recipes or one 8 segment process If you want only one Ramp use the Stra parameter You do not have to use the Pu Tr and TS parameters By...

Страница 4: ...FF time 0 0 to 100 0 Seconds oAt1 oAt2 Output scale 0 0 20mA connect parallel 500 ohm for 0 10VDC 1 4 20mA 0 Alarm output 1 Manual Automatic 2 Sensor break alarm 3 PV is out of range 4 Ramp Soak finis...

Страница 5: ...Time 100 Process Output Stun Start Value PID coefficients are determined and system becomes stable Start Value Set Value 2 Process Set Value Time STEP RESPONSE TUNING Self Tune Process Value Time 100...

Страница 6: ...ngeAlarm Process Output 100 50 0 Process Value Cooling Set Value Heating Set Value Process Output 100 50 0 Process Value Heating Set Value Cooling Set Value If 0 Dead Band If 0 Overlap Band 1 877 798...

Страница 7: ...ak time up to 8 R S steps Ramp Soak menu EMO 700 relay output module must be plugged into Module 1 socket 100 240 V Opening Relay N L Supply Switch Closing Common Opening Valve Supply Input M V n n Op...

Страница 8: ...C AUTO SET SET SET SET SET SET C AUTO C AUTO C AUTO C AUTO SET SET SET SET C AUTO C AUTO C AUTO C AUTO C AUTO SET SET SET SET SET SET Technician Parameters Process Input Configuration C AUTO C AUTO C...

Страница 9: ...Control Parameters Technician Parameters Input Output 1 Module Configuration P 9 C AUTO C AUTO C AUTO C AUTO C C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO SET SET SET SET SET...

Страница 10: ...ET SET C AUTO SET Technician Parameters Output 3 Configuration C AUTO C AUTO C AUTO C AUTO C C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO C AUTO SET SET SET SET SET SET SET SET SET SET SET...

Отзывы: