DynaPak 3010RNM Version 01102001 ATEX Rev.
YZ Systems, Inc. • 3101 Pollok Drive • Conroe, Texas • USA • 77303 • P: 936.788.5593 • F: 936.788.5720
Timer Mode
10.1 Mechanical Operation Test:
A. Set the mode switches as follows:
1. Positions 1, 2 and 3 on.
B. Set the time switches to 00 to enter the
diagnostic mode. This mode enables the user
to increase the solenoid output rate to one
pulse every two seconds.
10.3 LCD Stroke Indicator Test Mode:
A. To test the stroke counter, set the mode
switches as follows:
1. Positions 1, 2 and 3 on.
B. Set the time switches to 00.
C. Unscrew the thumbscrews and remove the
six position terminal strip and cover. This will
expose the battery pack and the three position
configuration jumper (located in the lower right
corner of the Z-65/6.1 controller assembly).
D. Set the configuration jumper to the far right
position marked stroke indicator test.
E. This will cause all six digits to become active
on the stroke counter. Depress the reset. The
stroke counter should increment 000000,
111111,
etc., up to 999999 each time the
solenoid fires. When the counter display reads
999999, the test is complete.
Note: when the test is complete, move the
jumper back to the factory position (far left
position).
Factory
System
Approved
Mutual
Approved
Factory
System
Factory
Approved
Mutual
System
10. Troubleshooting:
10.3d Jumper Switch Location