background image

Install-MONTE_BASE - SEP_2015.doc                  www.yunca.co.nz  

Page 1 of 4 

 

 

A division of Terry Young Ltd, New Zealand 

 

INSTALLATION INSTRUCTIONS for 

MONTE BASE  

WOOD BURNER 

• Clean Air Sub 1.0    • Clean Air WET Sub 1.0     

• Clean Air Sub 0.7    • Non Clean Air (Rural).

 

 

SEPTEMBER 2015 

TESTED in compliance with AS/NZS 2918: 2001

  

A

. Yunca recommends that competent trades persons carry out all installations (e.g. 

NZHHA Registered Installer), to obtain maximum performance and safe, efficient heating. 

B

. A permit is required and we suggest you check with local building inspectors as by-laws 

do vary from area to area.  

Also notify your Insurance Company that a solid fuel heater has been installed. 

 

C

. Floor Protector 

–  

1.  Must extend a minimum of 300mm in front of the fuel-loading or ash-removal opening. 
2.  Must extend at least 200mm from each side of the fuel-loading or ash-removal opening 

unless it forms an abutment with a wall or heat shield at a lesser distance. 

3. 

Ash Floor Protector must be constructed of non-combustible materials.

 

 

D

. Seismic restraint 

– Heater must be restrained from seismic movement as required by AS/NZS   

                                   2918:2001. 10mm diameter bolting holes in the rear corners allow restraint. 

 

E.

 Manufacturers recommended tested minimum clearances from combustible walls. 

 

Tested to AS/NZS 2918 : 2001 by APPLIED RESEARCH SERVICES LTD 

Clearance 

Rear Clearance (with YUNCA STD FLUE GUARD fitted) 

200mm 

Side Clearance (with YUNCA STD FLUE GUARD fitted) 

450mm 

Corner Clearance (with YUNCA STD FLUE GUARD fitted) 

280mm 

 

F. YUNCA Flue Kit (Complies with AS/NZS 2918:2001 Appendix F): FIG A, B & E

 

1

. 4.2m x 150mm stainless steel flue. 

4

. 1 x insulation boundary shield. 

2

. 2.4m x 250mm galvanised liner. 

5. 

2 x spider brackets. 

3.

 1 x ceiling tile (430mm x 430mm). 

6.

 1 x weather cap & cowl. 

 

Please Note: 

All flue joints must be sealed with flue sealing compound. Use stainless 

steel screws or rivets to join the flue pipe (three equally spaced places at each joint). The 
first length of flue must be fixed to the flue spigot with at least one stainless steel screw 
or rivet. The required minimum flue termination height is 4.6 m above the floor protector. 

 

G.  MONTE  WOODBURNER  Flue  Mounted  Shield  (Flue  Guard)  Kit.  Complies  (with 

heater) to AS/NZS 2918:2001): Refer FIG A 

1 x 1200mm length lined back guard, plus an 

optional

 adjustable 900mm extension. 

1 x 1200mm length perforated front guard. 
1 x 1200mm length tertiary back guard with spacers. 
1 x top front deflector shield (half round shaped, angled 30 degrees when installed). 

 

Please Note: The minimum Flue Mounted Shield Height is 1200mm. 

Содержание MONTE BASE Clean Air Sub 1.0

Страница 1: ...straint E Manufacturers recommended tested minimum clearances from combustible walls Tested to AS NZS 2918 2001 by APPLIED RESEARCH SERVICES LTD Clearance Rear Clearance with YUNCA STD FLUE GUARD fitted 200mm Side Clearance with YUNCA STD FLUE GUARD fitted 450mm Corner Clearance with YUNCA STD FLUE GUARD fitted 280mm F YUNCA Flue Kit Complies with AS NZS 2918 2001 Appendix F FIG A B E 1 4 2m x 150...

Страница 2: ...ss than 600mm above the highest point on the roof if within 3 0m of that point or Not less than 1000mm above the intersection point with the roof and not lower than any point of the roof within 3 0m In any case the length of the flue shall not be less than 4 6m from the ash floor protector In some situations the Local Council may vary the above requirements 2 The flue system must be tested and com...

Страница 3: ...UNTED SHIELD FITTED Measurements in millimetres A B E F G H 200 450 280 366 782 600 FIG D MINIMUM FLOOR PROTECTION MEASUREMENTS WITH YUNCA FLUE MOUNTED SHIELD FITTED Measurements in millimetres C D J K L M N O P 300 125 913 999 1481 1288 633 663 699 Note All Dimensions are in millimetres Above Non combustible wall clearances Brick lining From the floor to within 25mm of ceiling Leave air vents at ...

Страница 4: ...E MARKING TESTED TO AS NZS 4013 C ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AS NZS 4013 D MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS WHERE SUCH ACTION IS...

Отзывы: