CAUTION
:
Do not use any smoke
pipes less than 24 gauge between
furnace and chimney.
WARNING
:
No damper, heat saver, or
automatic vent damper device should be
installed in or on smoke pipe. Except the
barometric draft regulator.
CONNECTING SMOKE PIPE
Set the smoke pipe end of the furnace as close to the
chimney as possible. The rise of the smoke pipe
toward the chimney must be at least one inch per
linear foot of pipe. Do not exceed 10 feet in length.
A clean out tee should be installed for removal of soot
and fly ash.
NOTE: Service clearance of at least 24 inches is
required to service blower and motor and clean out
the secondary heat exchanger.
Do not install smoke pipe longer than necessary to
reach chimney. This is for purposes of trapping heat.
The smoke outlet temperature is designed to carry
by-products of combustion out through chimney.
The smoke pipe must not pass through any
combustible material.
The smoke pipe entrance into a masonry chimney should
be at least 2 feet above the clean out. The smoke pipe
must not extend into the chimney beyond the inner face
of the chimney liner.
LESSER CLEARANCES TO COMBUSTIBLE
MATERIALS ALLOWED
This furnace is UL Listed, requiring 18 inches from smoke
pipe to a combustible surface. A reduction of 9 inches
from a combustible ceiling and 12 inches from a
combustible wall is allowed if the space is insulated
according to NFPA 90B, table 6-5.1.2.
WARNING
:
DO NOT CONNECT THIS
FURNACE TO A CHIMNEY SERVING
ANOTHER APPLIANCE
34
WARNING
Check your chimney. The chimney is a
very important part of your heating system.
It must be the right size, properly construct-
ed and in good condition. No furnace can
function properly with a bad chimney. The
chimney must supply a draft of .03 Water
Column. If possible, use a 15 foot or
higher chimney. Add an additional foot to
the chimney for each 1,000 feet of eleva-
tion above sea level.
Installation
Содержание LWO-112
Страница 9: ...9 Furnace Features Eagle I Husky...
Страница 11: ...11 Furnace Features Eagle II Polar...
Страница 31: ...OIL AND WOOD COAL HEATING WITH A C 31 Wiring Diagrams DS 103 DAMPER CONTROL...
Страница 32: ...GAS AND WOOD COAL HEATING ONLY 32 Wiring Diagrams DS 103 DAMPER CONTROL...
Страница 33: ...GAS AND WOOD COAL HEATING WITH A C 33 Wiring Diagrams DS 103 DAMPER CONTROL...
Страница 56: ...EAGLE I HUSKY MODELS LWO 112 LWG 112 56 Exploded Views Parts Lists...
Страница 58: ...EAGLE II POLAR MODELS LWO 168 LWG 168 58 Exploded Views Parts Lists...
Страница 62: ...WAYNE MODEL P250AF DIN GAS BURNER 62 Exploded Views Parts Lists...