41
SP2
Setpoint 2
When I2 module installed in MIO slot, SP1 and SP2 can be switched by an external
switch. If the switch is off, SV=SP1; if the switch is on, SV=SP2.
SPH
SPr
Ramp Slope
limit (Only for
AI-526P)
Once SPr was set, if PV<SV when program start, the first step of ramp slope will
limited by SPr value until the temperature reach the first SV , under this limitation, the
RUN lamp will keep flashing.
For Ramp mode. SPr had effect on first step only.
For Soak mode, SPr had effect on each step.
0~3200
℃
/
Min
Pno
No. of Program
step (Only for
AI-526P)
To define the number of program in use.
Pno= 0,
disable the program running mode, then AI-526P will same as AI-526,
meanwhile, can set the parameter “SPr” to limit the ramp time.
Pno
=
1~30
, AI-526P working as normal programmable controller
0~30