54
When set
-XXX.1, AL1 activate, AL2 release
-XXX.2, AL1 release, AL2 activate
-XXX.3, AL1 and AL2 activate
-XXX.4, AL1 and AL2 release
Example:
Example 1 : t -5 = -1.1 ; means when the program arrived step 5, AL1 activate, AL2 release and
will jump to step 1 continues running
Example 2 : t-6 = -0.3 ; means when the program arrived step 6, AL1 and AL2 activate and
continuous next step.
Note:
The program will be held if it jump from a control segment to another control segment (an Hold action will be
inserted between two control sections), external run/Hold operation is needed to release the Hold status. It is not
allowed that the jump section jump to itself (for example: t -6= -6), otherwise, the Hold status cannot be released.
Program arrangement of multi-curve operation
AI-526P
has the advanced function of flexible program arrangement. Normally, when the program stops, the StEP will
be automatically set to1. Thus if StEP is not change to other value, a program will start from step1. If multiple curves
are defined, the control can jump to different curve by setting step 1 as jump segment.
For example:
There are three curves with the length of 3 steps represent three groups of process parameter, they are
Содержание AI-526