at the beginning of power on. 

Proportion band 

Proportion band in PID with unit 

or 

  but not the percentage of the 

input scale. 

1~999 

30 

Time of integral 

Time of integral in PID. No integral effect when I=0 

0~9999 

sec 

100 

Time of derivative 

Time of derivative in PID with unit 0.1 second. No derivative effect when 
d=0 

0~9999 

sec 

50.0 

Ctl 

Control period 

Smaller value will result in higher control accuracy.   
For SSR output, generally 0.5 to 3 seconds. 
For Relay output, generally 15 to 40 seconds, because small value will 
cause the frequent On-Off of mechanical switch and shorten its service 
life.    Ctl  is  recommended  to  be  1/4 

  1/10  of  derivative  time.  When 

control  under  on-off  control,  Ctl  is  used  as  delay  time  to  restart  to 
protect the compressor.   

0.5-300 

sec 

 

CHYS 

Control 

hysteresis 

To avoid frequent relay on-off action, in ON-OFF control mode. 
PV > SV, Output turns OFF (Relay opens) 
PV < SV-CHY, Output turns ON (Relay closes) 

0~200 

 

InP 

Input 

specification 

 

Thermocouples & RTD 

21 

Pt100 

 

0

21 

dPt 

Resolution 

0 or 0.0 selectable. 0.0 is valid for 0~99.9 

 

  display   

0/0.0 

0.0 

Scb 

Input shift 

Scb  is  used  to  make  input  shift  to  compensate  the  error  produced  by 
sensor or input signal. 
PV after compensation= PV before compen Scb. 

-200

+400 

FILt 

PV input filter 

Higher degree of FIL gives more powerful noise filtering.     
Large  FIL  value  stabilized  the  input  signal  but  the  system  response 
speed will be slow. Generally speaking, 1 to 3 will be used. 
If  great  interference  exists,  FIL  can  be  gradually  increase  to  limit  the 
momentary fluctuation among 2 to 5 unit. 
When the instrument is being metrological verified, FIL should be set to 
0 or 1 to minimize the response time. 

0

40 

Fru 

Selection of 

power frequency 
and temperature 

scale 

50C: 50Hz, 

 

50F: 50Hz, 

 

60C: 60Hz, 

 

60F: 60Hz, 

 

 

50C 

SPL 

Lower limit of SV 

Minimum value that SV allowed to be.   
When SPH=0, the SV range will 0~400

 

-999 ~ 
+3000 

SPH 

Upper limit of SV 

Maximum value that SV allowed to be.   
When SPH=400, the SV range will 0~400

 

400 

 

Содержание AI-218

Страница 1: ...Automation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 218 Opera...

Страница 2: ...Multiple thermocouples and RTDs are selectable Maximum support two alarms contact output Universal supply power 100 240VAC 50Hz 60Hz 2 Part 2 Front panel dimension Panel Size Front Panel width height...

Страница 3: ...tput L5 Dual relay output module Output module Capacity 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to relay output L or S...

Страница 4: ...s The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press will access System Parameter Table See V PARAMETER AND SETT...

Страница 5: ...o 808 and press to unlock the System Parameter Table 0 255 0 System Parameter Table Loc 808 to unlock AHYS Alarm Hysteresis Avoid frequent alarm on off action because of the fluctuation of PV AHY 2 by...

Страница 6: ...ction in ON OFF control mode PV SV Output turns OFF Relay opens PV SV CHY Output turns ON Relay closes 0 200 InP Input specification Thermocouples RTD 0 K 1 S 2 R 4 E 5 J 7 N 21 Pt100 0 21 0 dPt Resol...

Страница 7: ...nel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermocouples compensate wires should be directly screwed...

Отзывы: