background image

  Yudian (H.K.) Automation Technology Co. Ltd. 

                                                                                       

Website: 

http://www.yudian.us

   

http://www.yudian.com.hk

  

                                                                                                                                                                      Email: 

[email protected]

  

Tel: +852-2770 8785      Fax: +852-2770 8796 

 

V. PARAMETER AND SETTING

 

 

 

Parameter

 

Title 

Description 

Range 

Default 

Field Parameter Table (Press and hold 

 

for 2 seconds to access) 

 

HIAL 

High limit alarm 

Alarm on when PV (Process Value) >HIA;   
alarm off when PV<HIA-AHY 

-999 

 

+3000 

3000 

LoAL 

Lower limit alarm 

Alarm on when PV (Process Value) < LoA;   
alarm off when PV > LoA+AHY 

-999 

HdAL 

Deviation high 

alarm 

Alarm on when PV-SV>HdA;   
alarm off when PV-SV<HdA-AHY 

3000 

LdAL 

Deviation low 

alarm 

Alarm on when PV-SV<LdA;   
alarm off when PV-SV>LdA+AHY 

-999 

Loc 

Parameter lock 

Loc=0:  Allowed  to  change  field  parameters,  SV  and  activate  AT 
function. 
Loc=1: Allowed to change field parameters, SV but no AT activation. 
Loc=2:  Allowed  to  change  field  parameters  but  not  allowed  to  set  SV 

nor AT. 

Loc=4~255: NOT allowed to change any parameters nor SV. 
Loc=808, Set to 808 and press 

 to unlock the System Parameter Table

0

255 

System Parameter Table (Loc=808 to unlock)

 

 

AHYS 

Alarm Hysteresis 

Avoid frequent alarm on-off action because of the fluctuation of PV 
AHY=2 by default. 

0~200 

AoP 

Alarm output 

assignment 

Example: 

AOP    =        0                  4                  0                3     

                    LdAL          HdAL          LoAL          HIAL 

It shows that HIAL is sent to AU1, HdAL to AU2, LoAL and LdAL has no 

output. 

Alarm 

Output to   

LdAL       

(x 1000) 

HdAL 

(x100) 

LoAL 

(x10) 

HIAL 

(x1) 

None 

AL1 

AL2 

AU1 

AU2 

0~4444 

Depend 

on 

module 

CtrL 

Control mode 

 

onF  :  ON-OFF  control. When  PV>SV,  output  stops  and  heating 
stops. When PV<SV-AHY, output resumes. 

 

AI  :  AI-PID  control.  The  output  time  proportion  can  adjusted  by 
parameter Ctl 

onoF/API

APId 

Act 

Acting method 

rE: Reverse acting. Increase in measured variable causes a decrease 

in the output, such as heating control. 

dr: Direct acting. Increase in measured variable causes an increase in 

the output, such as refrigerating control. 

rEb: Reverse acting with low limit alarm and deviation low alarm 

blocking at the beginning of power on. 

drb: Direct acting with high limit alarm and deviation high alarm blocking 

rE , dr ,   

rEb, drb 

rE 

Содержание AI-218

Страница 1: ...Automation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 218 Opera...

Страница 2: ...Multiple thermocouples and RTDs are selectable Maximum support two alarms contact output Universal supply power 100 240VAC 50Hz 60Hz 2 Part 2 Front panel dimension Panel Size Front Panel width height...

Страница 3: ...tput L5 Dual relay output module Output module Capacity 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to relay output L or S...

Страница 4: ...s The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press will access System Parameter Table See V PARAMETER AND SETT...

Страница 5: ...o 808 and press to unlock the System Parameter Table 0 255 0 System Parameter Table Loc 808 to unlock AHYS Alarm Hysteresis Avoid frequent alarm on off action because of the fluctuation of PV AHY 2 by...

Страница 6: ...ction in ON OFF control mode PV SV Output turns OFF Relay opens PV SV CHY Output turns ON Relay closes 0 200 InP Input specification Thermocouples RTD 0 K 1 S 2 R 4 E 5 J 7 N 21 Pt100 0 21 0 dPt Resol...

Страница 7: ...nel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermocouples compensate wires should be directly screwed...

Отзывы: