Ctl Control
period
Smaller value will result in higher control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 seconds, because small value will
cause the frequent On-Off of mechanical switch and shorten its service
life. Ctl is recommended to be 1/4 – 1/10 of derivative time. When
control under on-off control, Ctl is used as delay time to restart to
protect the compressor.
0.5-300 sec
CHY
Control
hysteresis
To avoid frequent relay on-off action, in ON-OFF control mode.
PV > SV, Output turns OFF (Relay opens)
PV < SV-CHY, Output turns ON (Relay closes)
0~200
InP
Input
specification
Thermocouples & RTD
0
K
4
E
5
J
7
N
21
Pt100
0
~
21
dPt
Resolution
0 or 0.0 selectable. 0.0 is valid for 0~99.9
℃
/
℉
display
Scb Input
shift
Scb is used to make input shift to compensate the error produced by
sensor or input signal.
PV after compensation= PV before compen Scb.
-99
~
+99
℃
FIL
PV input filter
Higher degree of FIL gives more powerful noise filtering.
Large FIL value stabilized the input signal but the system response
speed will be slow. Generally speaking, 1 to 3 will be used.
If great interference exists, FIL can be gradually increase to limit the
momentary fluctuation among 2 to 5 unit.
When the instrument is being metrological verified, FIL should be set to
0 or 1 to minimize the response time.
0
~
40
Fru
Selection of
power frequency
and temperature
scale
50C: 50Hz,
℃
50F: 50Hz,
℉
60C: 60Hz,
℃
60F: 60Hz,
℉
SPH
Upper limit of SV
Maximum value that SV allowed to be.
When SPH=400, the SV range will 0~400
℃
0
~
999
℃