Ctl Control 

period 

Smaller value will result in higher control accuracy.   

For SSR output, generally 0.5 to 3 seconds. 

For Relay output, generally 15 to 40 seconds, because small value will 

cause the frequent On-Off of mechanical switch and shorten its service 

life.  Ctl is recommended to be 1/4 – 1/10 of derivative time. When 

control under on-off control, Ctl is used as delay time to restart to 

protect the compressor.   

0.5-300 sec 

CHY 

Control 

hysteresis 

To avoid frequent relay on-off action, in ON-OFF control mode. 
PV > SV, Output turns OFF (Relay opens) 
PV < SV-CHY, Output turns ON (Relay closes) 

0~200 

InP 

Input 

specification 

 

Thermocouples & RTD 

21 

Pt100 

 

0

21 

dPt 

Resolution 

0 or 0.0 selectable. 0.0 is valid for 0~99.9 

℃ 

 display  

 

Scb Input 

shift 

Scb is used to make input shift to compensate the error produced by 
sensor or input signal. 
PV after compensation= PV before compen Scb. 

-99

+99

 

FIL 

PV input filter 

Higher degree of FIL gives more powerful noise filtering.     

Large FIL value stabilized the input signal but the system response 

speed will be slow. Generally speaking, 1 to 3 will be used. 

If great interference exists, FIL can be gradually increase to limit the 

momentary fluctuation among 2 to 5 unit. 

When the instrument is being metrological verified, FIL should be set to 

0 or 1 to minimize the response time. 

0

40 

Fru 

Selection of 

power frequency 

and temperature 

scale 

50C: 50Hz, 

 

50F: 50Hz, 

 

60C: 60Hz, 

 

60F: 60Hz, 

 

 

SPH 

Upper limit of SV 

Maximum value that SV allowed to be.   
When SPH=400, the SV range will 0~400

 

0

999

 

 

Содержание AI-208

Страница 1: ...omation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 8 Ope...

Страница 2: ...tiple thermocouples and RTDs are selectable Suitable for 0 999 application Maximum support two alarms contact output Universal supply power 100 240VAC 2 Part 2 Front panel dimension Panel Size Front P...

Страница 3: ...city 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to SSR output G and no module option provided i e AI 208 D1 G AI 208 D1 G...

Страница 4: ...ously jumps out from parameter setting to the default status The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press...

Страница 5: ...ction because of the fluctuation of PV AHY 2 by default 0 200 AOP Alarm output assignment HdA x100 LdA LoA x10 HIA x1 0 0 0 1 AU1 1 AU1 1 AU1 2 AU2 2 AU2 2 AU2 5 AU1 AU1 6 AU2 AU1 7 AU1 8 AU2 9 AU1 AU...

Страница 6: ...s 0 200 InP Input specification Thermocouples RTD 0 K 4 E 5 J 7 N 21 Pt100 0 21 dPt Resolution 0 or 0 0 selectable 0 0 is valid for 0 99 9 display Scb Input shift Scb is used to make input shift to co...

Страница 7: ...ed is for upright panel dimension A A1 E E1 For panel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermoc...

Отзывы: