Yudian (H.K.) Automation Technology Co. Ltd.
Website:
http://www.yudian.us
http://www.yudian.com.hk
Email:
Tel: +852-2770 8785 Fax: +852-2770 8796
3. (Part 3 and 4) indicate the module installed in OUTP and AUX sockets.
Allowed modules in each socket are as below:
Allowed Type
Module Socket
N L
L0/L1
L5 G
3. OUTP (main output)
√
√
4. AUX (Auxiliary output)
√
√
√
N
(or none) no module installed
L
Relay contact output module (Capacity: 5A/250VAC, normal open)
L0/L1
Relay contact output module (Capacity: 2A/250VAC, normal open/normal close, spark
absorption at normal open, support AU1 alarm output)
L5
Dual relay output module Output module (Capacity: 2A/250VAC, normal open, support AU1 and
AU2 alarm output)
G
SSR voltage output module (30mA/5VDC)
* D1-sized controller is fixed to SSR output(G) and no module option provided, i.e. AI-208-D1-G,
AI-208-D1-G-L0 or AI-208-D1-G-L5 must be specified upon order.
II. TECHNICAL SPECIFICATION
1.
Input type : K, E, J, N
(thermocouples);
Pt100
(resistance temperature detector)
2.
Instrument Input range : K, E, J, N
(0~+999)
℃
,
Pt100
(0~+800)
℃
3.
Measurement accuracy :
0.3%FS±1
℃
4.
Temperature display resolution :
0 or 0.0 (0.0 just for 0~99.9 display)
5.
Control mode:
On-off control mode, or
PID control with auto-tuning.
6.
Type of Alarm:
High limit alarm, Lower limit alarm, Deviation High Alarm and Deviation Low Alarm
with alarm blocking at power on.
7.
Power supply voltage rating
: 100-240VAC, -15%, +10% / 50-60Hz.
8.
Power consumption:
≤
2W
9.
Ambient temperature:
-10~+60
℃
, Humidity: 0~90RH%