background image

  Yudian (H.K.) Automation Technology Co. Ltd. 

                                                                                       

Website: 

http://www.yudian.us

   

http://www.yudian.com.hk

  

                                                                                                                                                                      Email: 

[email protected]

  

Tel: +852-2770 8785   Fax: +852-2770 8796 

 

3.  (Part 3 and 4) indicate the module installed in OUTP and AUX sockets.

   

 

Allowed modules in each socket are as below: 

Allowed Type

Module Socket 

N L 

L0/L1

L5 G 

3. OUTP (main output) 

 

 

 

 

 

4. AUX (Auxiliary output) 

 

 

 

 

 

      (or none) no module installed   

L

 

Relay contact output module (Capacity: 5A/250VAC, normal open) 

L0/L1

 Relay contact output module (Capacity: 2A/250VAC, normal open/normal close, spark 

absorption at normal open, support AU1 alarm output) 

L5 

    Dual relay output module Output module (Capacity: 2A/250VAC, normal open, support AU1 and 

AU2 alarm output) 

G

 

SSR voltage output module (30mA/5VDC)   

* D1-sized controller is fixed to SSR output(G) and no module option provided, i.e. AI-208-D1-G, 

AI-208-D1-G-L0 or AI-208-D1-G-L5 must be specified upon order. 

II. TECHNICAL SPECIFICATION 

1.

 

Input type : K, E, J, N 

(thermocouples); 

Pt100 

(resistance temperature detector) 

2.

 

Instrument Input range :  K, E, J, N

 (0~+999)

Pt100

 (0~+800)

 

3.

 

Measurement accuracy : 

0.3%FS±1

 

4.

 

Temperature display resolution :

 0 or 0.0 (0.0 just for 0~99.9 display) 

5.

 

Control mode: 

 

On-off control mode, or 

PID control with auto-tuning. 

6.

 

Type of Alarm:

 High limit alarm, Lower limit alarm, Deviation High Alarm and Deviation Low Alarm 

with alarm blocking at power on. 

7.

 

Power supply voltage rating

: 100-240VAC, -15%, +10% / 50-60Hz. 

8.

 

Power consumption:

 

2W 

9.

 

Ambient temperature: 

-10~+60

, Humidity: 0~90RH% 

Содержание AI-208

Страница 1: ...omation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 8 Ope...

Страница 2: ...tiple thermocouples and RTDs are selectable Suitable for 0 999 application Maximum support two alarms contact output Universal supply power 100 240VAC 2 Part 2 Front panel dimension Panel Size Front P...

Страница 3: ...city 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to SSR output G and no module option provided i e AI 208 D1 G AI 208 D1 G...

Страница 4: ...ously jumps out from parameter setting to the default status The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press...

Страница 5: ...ction because of the fluctuation of PV AHY 2 by default 0 200 AOP Alarm output assignment HdA x100 LdA LoA x10 HIA x1 0 0 0 1 AU1 1 AU1 1 AU1 2 AU2 2 AU2 2 AU2 5 AU1 AU1 6 AU2 AU1 7 AU1 8 AU2 9 AU1 AU...

Страница 6: ...s 0 200 InP Input specification Thermocouples RTD 0 K 4 E 5 J 7 N 21 Pt100 0 21 dPt Resolution 0 or 0 0 selectable 0 0 is valid for 0 99 9 display Scb Input shift Scb is used to make input shift to co...

Страница 7: ...ed is for upright panel dimension A A1 E E1 For panel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermoc...

Отзывы: