5
Connectors in bad working condition can provoke fires. Make sure that the
connectors are in good working condition and verify that they are attached to the right
tightening torque.
Disconnect the batteries from the charger/rectifier before any maintenance
work. If necessary, disconnect one part of the batteries in series so that the potential
difference of the whole unit on which the operator is working is not more than 120V.
Mark out the work area to prevent non-authorised persons from entering.
2-5/ LIST OF PROTECTIVE MATERIAL
- Safety helmet (with visor).
- Safety boots.
- Handling gloves.
- Acid-resistant gloves.
- 1000V electrical protection gloves.
- Safety glasses anti-UV (EN166 and 170).
- Insulating mat or insulating stool.
- Anti-static and acid-resistant clothing.
- Insulated tools (NFEN 60 900, IEC 60900 or local equivalent).
- Insulated torque wrench.
- Insulated caps for wire ends.
- Individual eye-bath.
- Marking equipment.
- Lifting tools if necessary.
- Product for neutralising acid (for open batteries).
3/ RECEIPT OF A DELIVERY
3-1/ CONTROLS ON RECEIPT OF THE DELIVERY
Make sure that the number of packages corresponds to the delivery slip.
Make sure that the packages have not been damaged during transportation.
A damaged package may be the result of bad handling.