Smart Positioner
YT-2500 / 2550 / 2501 Series
Product manual
Ver. 1.04
49
ITEM
Description
FF / FS
YT-2500L
1’st row→FF: Fail Freeze / FS: Fail Safe.
2’nd row→Positioner model.
1.6.00
VERSION /
2016MR 8
1’st row→version number of firmware.
2’nd row→VERSION: Main software version / 2016MR 8: loading date
of software.
※
You can toggle them, pushing <ENTER>
HART V
HART protocol version
POL AddR
HART protocol channel address.
※
You can change it, pushing <ENTER>
4.18
0Y 0d
Total used time duration. If a unit was used less than 1 minute, the
time will not accumulate.
1’st row→”4.18” means 4hours and 18minutes.
2’nd row→0Y: years, 0d: days
3.12
FULL_OP
Time required (seconds) to fully open the current valve from the
closed state.
Saved after AUTO 1 or AUTO 2 Calibration.
2.97
FULL_CL
Time required (seconds) to fully close the current valve from the
opened state.
Saved after AUTO 1 or AUTO 2 Calibration.
VM NOR /
VM dIZ /
VM REV
Display types of valve stroke on LCD.
VM NOR : View Mode Normal. 4mA
0%, 20mA
100% display.
VM dIZ : Raw data
VM REV : View Mode Reverse. 4mA
100%, 20mA
0% display.
※
You can change it, pushing <ENTER>
Erro
Error code(C, D) or warning code(B, F, G, H).
Refer to 9.1 or 9.2 sections
ABS
Absolute resistance value.