9
8.
Secure enough space for maintenance (such as cleaning of strainer), inspections and repair as
shown below.
* Failure to follow this notice prevents maintenance, inspection and repair.
TSF-10
・
10F
TSF-11
・
11F
9. Slope the piping and place the product at as a low position as possible in order to make condensate
flow into the product by its own weight
.
10. To install the product in a main steam pipe, provide a drip leg at the inlet side of the product
.
11. Install a strainer (mesh size of 80 or more is recommended) at the inlet side of the product.
12.
Install the product so that it is not subjected to the shock of water hammer. Do not install a quick operating
valve before and/or after the product.
* Failure to follow this notice may result in malfunction due to damage to the float, or may result in scalds
or injury due to blow off when the product is subjected to an excessive shock and damaged.
13.
Install a bypass line.
* The system has to stop operation while inspection and maintenance of the product if the bypass line is
not installed.
200 mm or more
300 mm or more