Description

 

Correct

 

Incorrect

 

The  size  of  collecting 

condensate  pipe  should 
be  larger  than  the  sum 
area  of  each  discharge 
pipe.

 

And install check valves 

for  prevention  of  back 
flow.

 

 
 
 
 
 
 
 
 
 
 
 
 

 

For  condensate  recovery, 

connect  condensate  pipe  to 
the top of return pipe. 

Install  individual  return 

pipe for each pressure. 

And  install  check  valves 

for  prevention  of  back 
flow.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

Flash steam out from the high 

pressure  line  increases  back 
pressure of the trap on the low 
pressure line.

 

End  of  trap  discharge 

pipe  shall  be  positioned 
above the water level in 
the pit.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

 

While  stopping  the  trap  may 

suction  dirty  water  in  the  pit, 
which may lead to malfunction.

 

  

  

7.

 

Operating Procedure

 

7.1 Warning and Caution for Operation   

Warning

 

(1)

 

Before flow the steam in pipe line, make sure steam can flow without any dangerous at the end of pipe line. 

In case steam blow off, it may result in burns. 

(2)

 

When confirming product’s operation, do not stand in front of outlet.    Large amount of condensate may be 

discharged at the first steam flow. 

Blowing out of condensate can burn or injure you. 

Do not tighten the cap after flowing the fluids to the valve.   

(3)

 

Please do not tighten the cap. 

The gasket will be broken and leads to have a leakage. 

Содержание TD-10NA

Страница 1: ...us injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or moderate injury Caution may also be used to indicate other unsafe practices or risks of propert...

Страница 2: ...rating pressure range is considerably wide calling for no adjustment Any installation angles horizontal inclined or vertical are available permitting easy piping The trap is kept warm with insulation...

Страница 3: ...nsate temperature becomes almost equal to the saturated steam temperature the condensate passing through the bottom A of the disc becomes re evaporating jet Because of this a low pressure section is g...

Страница 4: ...e Capacity Installation 6 1 Warning and Caution for Installation Warning Plumb in the piping of the outlet side to the safe place where blowing steam condensate can not affect It is dangerous if fluid...

Страница 5: ...lower than discharging condensate has By pass line provided in parallel to the trap can give such advantages as follows By opening the by pass valve large volume of condensate and air on start up can...

Страница 6: ...positioned at the bottom of condensate producing device Condensate from every device shall be trapped independently The inlet and outlet piping shall be the same nominal size as a nominal size of the...

Страница 7: ...pipe shall be positioned above the water level in the pit While stopping the trap may suction dirty water in the pit which may lead to malfunction Operating Procedure 7 1 Warning and Caution for Opera...

Страница 8: ...hen repair the product proper parts must be used And do not alter product Using the improper parts and alternation of the product may be result on injury or burns by breakage of product blowing out of...

Страница 9: ...matter stuck or oil film on the disc and valve seat Disassemble and clean it Refer to 8 4 Disassembly Drawing about the name of parts mentioned above Contact us or our agent if necessity of parts rep...

Страница 10: ...of the body for TD 30NA differs Part names shown in boxes are consumable items Disposal When dispose the products we recommend each parts is disposed after checking what the material is Please refer...

Отзывы: