EPDT-241

 

 

 

5. Nominal Size Selection Table 

 

5.1 For steam (at saturated temperature) 

<Pressure vessel structure standards>                                                                                       

 

    [kg/h] 

Nominal 

size 

Set pressure [MPa] 

0.05 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

65A 

263 

340 

493 

663 

834 

1000 

1165 

1328 

1489 

1651 

1814 

80A 

350 

452 

657 

882 

1111 

1331 

1550 

1767 

1983 

2198 

2415 

100A 

622 

804 

1168 

1569 

1975 

2367 

2756 

3142 

3525 

3908 

4294 

125A 

972 

1257 

1826 

2451 

3086 

3699 

4307 

4910 

5508 

6107 

6709 

150A 

1400 

1810 

2629 

3530 

4445 

5327 

6203 

7071 

7932 

         

           

         

[kg/h] 

Nominal 

size 

Set pressure [MPa] 

1.1 

1.2 

1.3 

1.4 

1.5 

65A 

1976 

2138 

2299 

2461 

2621 

80A 

2631 

2846 

3060 

3276 

3489 

100A 

4677 

5059 

5440 

5825 

6203 

125A 

7309 

7906 

8500 

9102 

9692 

150A 

     

 

   

 

         

 

         

 

         

 

         

 
 

<Boiler structure standards>                                                                                                                [kg/h] 

Nominal 

size 

Set pressure [MPa] 

0.05 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

65A 

255 

332 

486 

640 

796 

947 

1101 

1254 

1407 

1557 

1710 

80A 

339 

442 

647 

851 

1059 

1261 

1466 

1670 

1873 

2073 

2276 

100A 

604 

786 

1150 

1514 

1884 

2242 

2607 

2968 

3330 

3686 

4047 

125A 

944 

1228 

1797 

2366 

2944 

3504 

4074 

4638 

5204 

5760 

6324 

150A 

1359 

1769 

2588 

3407 

4239 

5046 

5866 

6680 

7494 

         

 

         

 

[kg/h] 

Nominal 

size 

Set pressure [MPa] 

1.1 

1.2 

1.3 

1.4 

1.5 

65A 

1862 

2013 

2164 

2317 

2469 

80A 

2479 

2680 

2881 

3084 

3286 

100A 

4407 

4765 

5122 

5483 

5843 

125A 

6886 

7446 

8003 

8567 

9129 

150A 

 

         

   

         

 

         

 

         

 

         

 
 
 
 
 

 

Содержание AL-6

Страница 1: ...ates a potentially hazardous situation that if not avoided could result in death or serious injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or modera...

Страница 2: ...e seat leakage The product has allowable valve seat leakage and does not close completely valve seat leakage cannot be zero 2 Do not use the product for equipment or device which vibrates excessively...

Страница 3: ...sions mm Weight kg d L H1 H 65A 331 9 65 120 120 479 20 2 80A 441 8 75 130 130 132 493 495 24 0 100A 785 4 100 160 150 152 626 628 44 0 125A 1227 2 125 200 205 207 835 837 88 0 150A 1767 2 150 210 215...

Страница 4: ...e of the safety relief valve decreases when the fluid is released into the atmosphere by the pop action of the valve 5 the force of fluid lift is lowered At this point the repelling force of the sprin...

Страница 5: ...Pa 1 1 1 2 1 3 1 4 1 5 65A 1976 2138 2299 2461 2621 80A 2631 2846 3060 3276 3489 100A 4677 5059 5440 5825 6203 125A 7309 7906 8500 9102 9692 150A Boiler structure standards kg h Nominal size Set press...

Страница 6: ...ngs if the product is installed on a place where there is a risk that fluid blowout causes alarm activation or contamination of the peripheral equipment Improper placement may cause contamination of t...

Страница 7: ...h the open end of the exhaust pipe Failure to follow this notice may result in injury due to discharge Be aware that the product makes a loud noise at start up 4 Do not disassemble the product Please...

Страница 8: ...please contact us for repair at our factory 2 Damage on contact surface between valve 5 and valve seat 4 2 The product needs to be disassembled and its parts need to be replaced Please contact us for...

Страница 9: ...nd cleaned Please contact us 4 There is a back pressure at the piping of the product outlet 4 Remove the back pressure In addition change the piping layout not to allow back pressure 5 The product doe...

Страница 10: ...pair at our factory After lever operation the product does not stop blowing even if letting go of the lever 1 Scale stuck on contact surface between valve 5 and valve seat 4 1 Remove the scale by oper...

Отзывы: