Yoshitake AL-6 Скачать руководство пользователя страница 4

                                                                                  ■

EPDT-241

 

 

 

3. Structure 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig.2 Structure 

 

 

4. Operation 

 

 

Blowout operation   
As inlet pressure of the product rises and approaches opening pressure, the force of fluid pushing up the 
valve  [5]  approaches  the  force  of  the  spring  [12]  pressing  down  the  valve  [5],  and  then  the  product 
commences to blow. The fluid starts to leak by the simmering and accumulates gradually on the pressure 
groove. When the fluid pressure reaches the specified opening pressure the valve [5] pops. 
 

 

Closing operation 
Since  the  inlet  pressure  of  the  safety  relief  valve  decreases  when  the  fluid  is  released  into  the 
atmosphere by the pop action of the valve [5], the force of fluid lift is lowered. At this point, the repelling 
force of the spring [12] becomes larger than the force of fluid lift and thus the valve closes. In addition, 
since  the  safety  relief  valve  blows,  the  pressure  of  fluid  entering  into  the  back  of  the  valve  [5]  (back 
pressure) adds to the closing force. 

No. 

Part name 

1    Body 
2    Spring case 
3    Cap 
4    Valve seat 
5    Valve 
6    Spindle 
7    Guide plate 
8    Spindle guide 
9    Spring plate 

10    Adjusting screw 
11    Lock nut 
12    Spring 
14    Lever 
15    Stud bolt & nut 
16    Pin 
17    Nut 
18    Bolt   
19    Plug 
20    Name Plate 
21    Gasket 
22    Split pin 
23    Spindle Ring 
24    Rivet 

 

 

Содержание AL-6

Страница 1: ...ates a potentially hazardous situation that if not avoided could result in death or serious injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or modera...

Страница 2: ...e seat leakage The product has allowable valve seat leakage and does not close completely valve seat leakage cannot be zero 2 Do not use the product for equipment or device which vibrates excessively...

Страница 3: ...sions mm Weight kg d L H1 H 65A 331 9 65 120 120 479 20 2 80A 441 8 75 130 130 132 493 495 24 0 100A 785 4 100 160 150 152 626 628 44 0 125A 1227 2 125 200 205 207 835 837 88 0 150A 1767 2 150 210 215...

Страница 4: ...e of the safety relief valve decreases when the fluid is released into the atmosphere by the pop action of the valve 5 the force of fluid lift is lowered At this point the repelling force of the sprin...

Страница 5: ...Pa 1 1 1 2 1 3 1 4 1 5 65A 1976 2138 2299 2461 2621 80A 2631 2846 3060 3276 3489 100A 4677 5059 5440 5825 6203 125A 7309 7906 8500 9102 9692 150A Boiler structure standards kg h Nominal size Set press...

Страница 6: ...ngs if the product is installed on a place where there is a risk that fluid blowout causes alarm activation or contamination of the peripheral equipment Improper placement may cause contamination of t...

Страница 7: ...h the open end of the exhaust pipe Failure to follow this notice may result in injury due to discharge Be aware that the product makes a loud noise at start up 4 Do not disassemble the product Please...

Страница 8: ...please contact us for repair at our factory 2 Damage on contact surface between valve 5 and valve seat 4 2 The product needs to be disassembled and its parts need to be replaced Please contact us for...

Страница 9: ...nd cleaned Please contact us 4 There is a back pressure at the piping of the product outlet 4 Remove the back pressure In addition change the piping layout not to allow back pressure 5 The product doe...

Страница 10: ...pair at our factory After lever operation the product does not stop blowing even if letting go of the lever 1 Scale stuck on contact surface between valve 5 and valve seat 4 1 Remove the scale by oper...

Отзывы: