SECTION 7 - OPERATION
JOHNSON CONTROLS
117
Form 201.28-NM1.1
Issue date: 08/06/2021
7
Table 15 -
YVAA operational and fault/inhibit codes
1
2
3
4
5
6
7
8
9
10
NOTES
Units have Native BACnet MS/TP, Modbus RTU, and N2 communications. No external Gateway is required for these interfaces unless the customer is using Connected Services.
BACnet Object Types: 0 = Analog In, 1 = Analog Out, 2 = Analog Value, 3 = Binary In, 4 = Binary Out, 8 = Device, 15 = Alarm Notification (0-127 are reserved ASHRAE Objects)
WC = Inches of water Column, CFM = Cubic Feet per Minute, FPM = Feet Per Minute, PSI = Pounds per Square Inch, Pa = Pascals, kPa = kiloPascals, PPM = Parts Per Million, kJ/kg = kiloJoules per kilogram
Values that are not applicable due to unit configuration and options will be sent as zero (0).
Modbus values are all of type signed. Scaling values in
x10
(Bold) indicate scaling in metric is x100. Scaling and signing may not be modified in the field.
YVAA YVFA YAGK Native 13 May 21
Property of Johnson Controls
Subject to change without notice.
4 of 5
Code Value
Operational Code
Code Value
Fault/Inhibit Code
Code Value
Fault/Inhibit Code (cont.)
63
Manual Override
0
No Fault Code
51
Low Discharge Superheat
64
Daily Schedule Shutdown
1
Low Ambient Temperature
52
Low Suction Pressure Smart Freeze
65
Unit Switch OFF
2
High Ambient Temperature
53
Isolation Valve Failed to Close Warning
66
Remote Controlled Shutdown
3
Low Chilled Liquid Temperature
54
Isolation Valve Failed to Open Fault
67
Loss of External Communications
4
VSD Initialization Failure
55
High Discharge Pressure Rate
68
Flow Switch Shutdown
5
Low RTC Battery Voltage
56
Condenser Fan VSD Warning
69
VSD Cooling Shutdown
6
Invalid Number of Compressors Selected
70
Serial Number Shutdown
7
VSD Communications Failure
71
8
Pre-charge Low DC Bus Voltage (Unit)
72
Discharge Superheat Recovery
9
Pre-charge DC Bus Voltage Imbalance (Unit)
73
10
High DC Bus Voltage (Unit)
74
No Run Permissive
11
Low DC Bus Voltage (Unit)
75
Anti-Recycle Timer Active
12
DC Bus Voltage Imbalance (Unit)
76
System Switch OFF
13
High VSD Ambient Temperature
77
System Not Running
14
Single Phase Input (Unit)
78
System Running
15
VSD Power Supply Fault
79
Discharge Pressure Limiting
16
VSD Logic Board Fault
80
Suction Pressure Limiting
17
Motor Current Overload (Hardware)
81
Motor Current Limiting
18
CT Plug Fault
82
Free Cooling
19
High Harmonic Filter Temperature
83
ISN/BAS Motor Current Limiting
20
Evap Anti-Freeze Pump Fault
84
Remote Motor Current Limiting
21
Low Heat Exchanger Temperature
85
System Shutting Down
22
86
VSD Pre-Charging
23
87
VSD Baseplate Temp Limiting
24
88
VSD Internal Ambient Temp Limiting
25
89
Sound Limiting
26
90
ISN Sound Limiting
27
High Discharge Pressure (Software)
91
Remote Sound Limiting
28
High Differential Oil Pressure
92
Pulldown Motor Current Limiting
29
Low Differential Oil Pressure
Code Value
Warning Code
93
Cooling Demand Shutdown
30
Low Suction Pressure
0
No Warning Set
94
Input Current Limiting
31
High Discharge Temperature
1
Quarterly Service Required - Contact JCI
95
ISN Input Current Limiting
32
2
Yearly Service Required - Contact JCI
96
Remote Input Current Limiting
33
Eductor Clog Fault
3
3 Year Service Required - Contact JCI
97
Pulldown Input Current Limiting
34
Sensor Failure
4
5 Year Service Required - Contact JCI
98
35
Low Motor Current
5
Replace Oil Filter
99
36
High Motor Temperature
37
Pre-charge Low DC Bus Voltage (System, Frame E/F)
38
Pre-charge DC Bus Voltage Imbalance (System, Frame E/F)
39
High DC Bus Voltage (System, Frame E/F)
40
Low DC Bus Voltage (System, Frame E/F)
41
DC Bus Voltage Imbalance (System, Frame E/F)
42
High Motor Current
43
Motor Current Overload (Software)
44
IGBT Gate Driver Fault
45
High Baseplate Temperature
46
Single Phase Input (System, Frame E/F)
47
VSD Run Signal Fault
48
High Discharge Pressure (Hardware - HPCO)
49
Low Suction Superheat
50
Control Voltage Fault
YVAA YVFA YAGK Native 13 May 21
Property of Johnson Controls
Subject to change without notice.
5 of 5
Содержание YVAA Style A
Страница 10: ...JOHNSON CONTROLS 10 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 34: ...JOHNSON CONTROLS 34 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 62: ...JOHNSON CONTROLS 62 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 183: ...JOHNSON CONTROLS 183 Form 201 28 NM1 1 Issue date 08 06 2021 Notes...