SECTION 9 - MAINTENANCE
JOHNSON CONTROLS
179
Form 201.28-NM1.1
Issue date: 08/06/2021
9
Table 32 -
Pressure transducer output voltage, measured signal to return at the transducer
Suction pressure transducer
(125 psig)
Discharge condenser liquid pressure and discharge
pressure transducer
(400 psig)
Pressure
Voltage
Pressure
Voltage
0
0.50
0
0.50
5
0.66
25
0.75
10
0.82
50
1.00
15
0.98
75
1.25
20
1.14
100
1.50
25
1.30
125
1.75
30
1.46
150
2.00
35
1.62
175
2.25
40
1.78
200
2.50
45
1.94
225
2.75
50
2.10
250
3.00
55
2.26
275
3.25
60
2.42
300
3.50
65
2.58
325
3.75
70
2.74
350
4.00
75
2.90
375
4.25
80
3.06
400
4.50
85
3.22
90
3.38
95
3.54
100
3.70
105
3.86
110
4.02
115
4.18
120
4.34
125
4.50
Содержание YVAA Style A
Страница 10: ...JOHNSON CONTROLS 10 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 34: ...JOHNSON CONTROLS 34 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 62: ...JOHNSON CONTROLS 62 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 201 28 NM1 1 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 183: ...JOHNSON CONTROLS 183 Form 201 28 NM1 1 Issue date 08 06 2021 Notes...