ADAPTIVE CAPACITY CONTROL DETAILS SCREEN
OVERVIEW
This screen displays more detailed information per-
taining to a Adaptive Capacity Control (ACC).
Requires a login access level of SER-
VICE.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the Variable Speed Drive
this is the data returned by the VSD Logic board.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC
input in Analog Remote mode, PWM signal in Digital
Remote mode, MicroGateway interface in ISN mode or
a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed pull-
down period if the value is non-zero.
VSD Output Frequency
Displays the frequency at which the VSD is operating
the motor.
Pre-Rotation Vane Position
Displays the pre-rotation vane position as a value be-
tween 0 and 100%.
Surge Count
The total number of surge conditions detected by the Adap-
tive Capacity Control. The surge events detected by the
Surge Protection feature are not included in this total
.
Delta P/P
The value calculated by the Condenser and Evaporator
pressures as reported by the Adaptive Capacity Control.
PROGRAMMABLE
Local Motor Current Limit
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the motor
current reaches this value, the pre-rotation vanes will
not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close
to reduce the current to this value.
00362VIP
FIG. 22
OptiView Control Center
Содержание YT Millennium
Страница 11: ...FORM 160 55 O1 920 11 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT...
Страница 35: ...FORM 160 55 O1 920 35 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 37: ...FORM 160 55 O1 920 37 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 63: ...FORM 160 55 O1 920 63 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 67: ...FORM 160 55 O1 920 67 YORK INTERNATIONAL 2 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT...
Страница 73: ...FORM 160 55 O1 920 73 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 111: ...FORM 160 55 O1 920 111 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 136: ...YORK INTERNATIONAL 136 FORM 160 55 O1 920 Operational Maintenance LD00470 FIG 61 ASSEMBLY OF DEHYDRATOR...
Страница 155: ...FORM 160 55 O1 920 155 YORK INTERNATIONAL NOTES...