![York YMB018 THRU 060 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/york/ymb018-thru-060/ymb018-thru-060_technical-manual_4253441016.webp)
246809-YTG-E-0507
16
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YMB03011
INDOOR COIL MODEL NO.
AHP30
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
26.3
28.5
28.4
31.2
34.1
28.3
29.2
29.4
32.2
35.2
30.3
29.9
30.4
33.1
36.3
S.C.
25.8
23.4
19.9
19.6
15.5
27.8
26.4
22.0
21.7
16.6
29.8
29.5
24.1
23.8
17.7
K.W.
1.5
1.5
1.5
1.5
1.6
1.5
1.5
1.5
1.5
1.6
1.5
1.5
1.5
1.6
1.6
75
T.C.
25.7
27.4
27.5
30.1
33.0
27.4
28.2
28.4
31.0
33.9
29.2
29.1
29.3
31.9
34.8
S.C.
25.1
23.0
19.5
19.2
15.1
26.9
25.8
21.6
21.3
16.5
28.7
28.6
23.7
23.3
17.8
K.W.
1.7
1.7
1.7
1.7
1.8
1.7
1.7
1.7
1.7
1.8
1.7
1.7
1.7
1.8
1.8
85
T.C.
25.0
26.4
26.5
29.1
31.8
26.6
27.3
27.4
29.9
32.6
28.1
28.2
28.3
30.7
33.4
S.C.
24.5
22.6
19.1
18.8
14.7
26.1
25.2
21.2
20.8
16.3
27.7
27.8
23.3
22.8
17.9
K.W.
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
2.0
2.0
95
T.C.
24.3
25.3
25.6
28.0
30.7
25.7
26.3
26.4
28.8
31.3
27.0
27.3
27.2
29.5
31.9
S.C.
23.8
22.2
18.7
18.4
14.3
25.2
24.6
20.8
20.4
16.1
26.6
27.0
22.9
22.4
18.0
K.W.
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.2
2.1
2.2
2.1
2.2
2.2
105
T.C.
22.9
24.0
24.3
26.7
29.3
24.1
25.1
25.0
27.3
29.9
25.4
26.2
25.8
28.0
30.4
S.C.
22.5
21.7
18.2
17.9
13.8
23.7
23.7
20.3
19.9
15.5
25.0
25.8
22.4
21.8
17.1
K.W.
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.5
115
T.C.
21.6
22.7
22.9
25.3
27.9
22.7
23.9
23.7
25.9
28.5
23.8
25.0
24.4
26.5
29.0
S.C.
21.2
21.2
17.8
17.4
13.4
22.3
22.9
19.9
19.3
14.8
23.5
24.6
22.0
21.2
16.2
K.W.
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
125
T.C.
20.2
21.5
21.6
24.0
26.6
21.2
22.6
22.3
24.5
27.1
22.1
23.8
23.1
25.1
27.6
S.C.
19.9
20.6
17.3
16.9
13.0
20.9
22.1
19.4
18.8
14.1
22.0
23.5
21.5
20.7
15.3
K.W.
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA12B
FC/MC35B
0.99
1.00
1.00
MA12B
FC/MC42B
0.99
1.00
1.00
MV12B
FC/MC35B
1.01
0.99
0.96
MV12B
FC/MC42B
1.01
0.99
0.96
AV36
–
1.01
0.99
0.96
F*FP040
–
0.99
1.00
1.00
–
FC/MC/PC35
0.99
1.00
1.00
–
HC36
1.00
1.00
1.00
–
HD36
1.00
1.00
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
PV8*B16
FC/MC/PC35B
1.01
1.00
0.96
P(C,V)9*B12
FC/MC/PC35B
1.01
1.00
0.96
PV8*B16
HC36
1.01
1.00
0.96
P(C,V)9*B12
HC36
1.01
1.00
0.96
PV8*A12
HD36
1.01
1.00
0.96
PV8*B16
HD36
1.01
1.00
0.96
PV8*C16
HD36
1.02
1.00
0.96
PV8*C20
HD36
1.02
1.01
0.96
PV9*A12
HD36
1.01
1.00
1.00
P(C,V)9*B12
HD36
1.01
1.00
0.96
P(C,V)9*C16
HD36
1.01
1.00
0.96
P(C,V)9*C20
HD36
1.01
1.00
0.96