246809-YTG-E-0507
20
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YMB06011
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1600
1800
2000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
54.0
55.2
55.2
60.7
64.4
56.4
57.0
56.5
62.3
65.6
58.7
58.7
57.7
63.9
66.7
S.C.
49.8
47.0
36.8
39.6
29.4
52.1
50.2
40.6
42.1
30.8
54.4
53.5
44.3
44.6
32.2
K.W.
2.9
2.9
3.0
3.0
3.1
3.0
2.9
3.0
3.0
3.1
3.0
2.9
3.0
3.0
3.1
75
T.C.
52.5
53.5
52.6
58.5
61.5
54.7
55.3
53.9
60.0
62.9
57.0
57.1
55.2
61.5
64.2
S.C.
48.2
45.9
36.6
38.4
28.4
50.4
49.1
39.9
41.0
30.0
52.6
52.2
43.3
43.5
31.6
K.W.
3.3
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
3.5
3.4
3.4
3.4
3.5
3.5
85
T.C.
50.9
51.8
50.1
56.2
58.7
53.0
53.7
51.4
57.6
60.2
55.2
55.5
52.7
59.1
61.7
S.C.
46.7
44.9
36.3
37.3
27.5
48.7
47.9
39.3
39.8
29.2
50.8
50.9
42.3
42.4
31.0
K.W.
3.7
3.8
3.8
3.9
3.9
3.8
3.8
3.8
3.9
4.0
3.8
3.8
3.9
3.9
4.0
95
T.C.
49.3
50.2
47.6
53.9
55.8
51.4
52.0
48.9
55.3
57.5
53.4
53.8
50.2
56.6
59.2
S.C.
45.1
43.9
36.0
36.1
26.6
47.1
46.8
38.7
38.7
28.5
49.0
49.6
41.3
41.2
30.4
K.W.
4.2
4.3
4.3
4.3
4.4
4.2
4.3
4.3
4.3
4.4
4.2
4.3
4.3
4.3
4.4
105
T.C.
46.9
47.7
44.9
51.1
52.9
49.0
49.3
46.2
52.3
54.3
51.0
50.9
47.5
53.6
55.8
S.C.
42.8
42.0
34.8
34.7
25.5
44.7
44.5
37.3
37.2
27.3
46.6
46.9
39.8
39.8
29.2
K.W.
4.8
4.9
4.9
4.9
5.0
4.8
4.9
4.9
4.9
5.0
4.8
4.9
4.9
5.0
5.0
115
T.C.
44.6
45.2
42.3
48.3
50.0
46.6
46.7
43.6
49.5
51.3
48.6
48.1
44.8
50.6
52.5
S.C.
40.7
40.2
33.5
33.3
24.5
42.4
42.2
35.9
35.8
26.2
44.2
44.2
38.3
38.3
28.0
K.W.
5.3
5.5
5.5
5.5
5.6
5.4
5.5
5.5
5.5
5.6
5.4
5.5
5.5
5.6
5.6
125
T.C.
42.3
42.8
39.7
45.6
47.2
44.2
44.0
40.9
46.6
48.2
46.2
45.3
42.2
47.6
49.3
S.C.
38.5
38.5
32.3
32.0
23.4
40.1
40.0
34.5
34.4
25.1
41.8
41.5
36.8
36.9
26.8
K.W.
5.9
6.0
6.1
6.1
6.2
6.0
6.1
6.1
6.1
6.2
6.0
6.1
6.1
6.2
6.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA20D
FC/MC60D
1.00
1.00
1.00
MA20D
MC61D
1.01
1.01
1.00
MV20D
FC/MC60D
1.00
0.98
1.00
MV20D
MC61D
1.01
0.99
1.00
AV/SV60
–
1.00
0.98
1.00
F*FV060
–
1.00
0.98
1.00
AHP/SHP60
–
1.00
1.02
1.00
–
HC60
1.00
1.00
1.00
–
HD60
1.00
1.01
1.00
–
MC61
1.01
1.01
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*D20
FC/MC/PC60D
0.99
0.95
1.00
PV8*C20
FC/PC60C
1.00
0.99
1.00
P(C,V)9*C20
FC/PC60C
0.99
0.95
1.00
PV8*C20
HC60
1.00
0.99
1.00
P(C,V)9*D20
HC60
0.99
0.95
1.00
PV8*C20
HD60
1.00
0.99
1.00
P(C,V)9*C20
HD60
0.99
0.96
1.00
P(C,V)9*D20
HD60
0.98
0.96
1.00
PV8*C20
MC61D
1.01
1.00
1.00
P(C,V)9*C20
MC61D
0.98
0.96
1.00
P(C,V)9*D20
MC61D
1.00
0.97
1.00