Johnson Controls
69
Section 5: Technical data
Form 150.72-ICOM6
Issue date: 12/19/2023
55
Table 12:
Electrical data without pumps, R-454B, continued
YLAA
V
Hz MCA Min. N/F
disc SW
Min. dual
elem. fuse
and CB
Max. dual
elem. CB
System 2
Compr. 1
Compr. 2
Compr. 3
Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
200
208
60
734
1,000
800
800
102.8 635 102.8 635 102.8 635
6
7.6
44
230
60
731
1,000
800
800
102.8 635 102.8 635 102.8 635
6
7.4
37
380
60
443
600
500
500
62.2 355 62.2 355 62.2 355
6
4.5
23.1
460
60
369
600
400
400
51.4 316 51.4 316 51.4 316
6
4
19
575
60
292
400
300
300
41.1 258 41.1 258 41.1 258
6
2.9
15.3
230
208
60
904
1,200
1,000
1,000
130.1 761 130.1 761 130.1 761
6
7.6
44
230
60
902
1,200
1,000
1,000
130.1 761 130.1 761 130.1 761
6
7.4
37
380
60
498
600
500
500
71.1 475 71.1 475 71.1 475
6
4.5
23.1
460
60
472
600
500
500
67.9 344 67.9 344 67.9 344
6
4
19
575
60
339
400
350
350
48.7 296 48.7 296 48.7 296
6
2.9
15.3