Johnson Controls
64
Form 150.72-ICOM6
Issue date: 12/19/2023
Section 5: Technical data
Table 11:
Electrical data without pumps, R-410A, continued
YLAA
V
Hz MCA Min. N/F
disc SW
Min. dual
elem. fuse
and CB
Max. dual
elem. CB
System 2
Compr. 1
Compr. 2
Compr. 3
Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
156
208
60
634
800
700
700
106.2 523 106.2 523
—
—
4
7.6
44
230
60
632
800
700
700
106.2 578 106.2 578
—
—
4
7.4
37
380
60
383
400
400
400
64.3 355 64.3 355
—
—
4
4.5
23.1
460
60
319
400
350
350
53.1 290 53.1 290
—
—
4
4
19
575
60
252
400
300
300
42.5 255 42.5 255
—
—
4
2.9
15.3
170
208
60
740
800
800
800
106.2 523 106.2 523 106.2 523
5
7.6
44
230
60
738
800
800
800
106.2 578 106.2 578 106.2 578
5
7.4
37
380
60
447
600
500
500
64.3 355 64.3 355 64.3 355
5
4.5
23.1
460
60
372
400
400
400
53.1 290 53.1 290 53.1 290
5
4
19
575
60
295
400
350
350
42.5 255 42.5 255 42.5 255
5
2.9
15.3
175
208
60
740
800
800
800
106.2 523 106.2 523 106.2 523
5
7.6
44
230
60
738
800
800
800
106.2 578 106.2 578 106.2 578
5
7.4
37
380
60
447
600
500
500
64.3 355 64.3 355 64.3 355
5
4.5
23.1
460
60
372
400
400
400
53.1 290 53.1 290 53.1 290
5
4
19
575
60
295
400
350
350
42.5 255 42.5 255 42.5 255
5
2.9
15.3
200
208
60
734
1,000
800
800
102.8 574 102.8 574 102.8 574
6
7.6
44
230
60
731
1,000
800
800
102.8 635 102.8 635 102.8 635
6
7.4
37
380
60
443
600
500
500
62.2 355 62.2 355 62.2 355
6
4.5
23.1
460
60
369
600
400
400
51.4 280 51.4 280 51.4 280
6
4
19
575
60
292
400
300
300
41.1 225 41.1 225 41.1 225
6
2.9
15.3
230
208
60
959
1,200
1,000
1,000
138.8 943 138.8 943 138.8 943
6
7.6
44
230
60
956
1,200
1,000
1,000
138.8 943 138.8 943 138.8 943
6
7.4
37
380
60
599
800
600
600
87.2 564 87.2 564 87.2 564
6
4.5
23.1
460
60
504
600
600
600
73
408
73
408
73
408
6
4
19
575
60
359
600
400
400
51.9 375 51.9 375 51.9 375
6
2.9
15.3
Notes:
• Reference PIN 59 for pump models.
• Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump.
• Does not include the control transformer.